Illustration - our own render; see the datasheet for exact details.
Rittal 2411.811 Brass Cable Gland M16 x 1.5, 5-10 mm Cable, for AX Enclosures, Pack of 15
- Brand:
- Rittal
- Part number:
- 2411.811
- EAN:
- 4028177810082
Nickel-plated brass cable gland with an M16 x 1.5 thread for cables 5 to 10 mm in diameter, rated IP 68 and supplied in a pack of 15. Rittal part number 2411.811.
- M16 x 1.5 thread, 7 mm long
- For cable diameters 5-10 mm
- IP 68 (5 bar, 30 min)
- Nickel-plated brass, -40 °C to +100 °C
- Pack of 15
22 in stock
UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 3-5 working days.
Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.
Project quantities or a lead time to check? Request a quote
Specifications
Protection
| IP rating | IP68 |
|---|
Dimensions
| Weight | 0.3 kg |
|---|---|
| Thread size | M16 |
| Cable diameter | up to 6 mm, 6-12 mm |
| Min cable diameter | 5 mm |
| Max cable diameter | 10 mm |
Construction
| Material | Brass |
|---|
Fit
| Fits enclosure family | Rittal AX sheet steel, Rittal AX stainless steel, Rittal AX GRP |
|---|
What's supplied
| Pack quantity | Pack of 15 |
|---|
Identification
| Brand | Rittal |
|---|---|
| Part number | 2411.811 |
| EAN | 4028177810082 |
| Range | Rittal AX |
| Type | Cable gland |
More technical data
| Thread | M16 x 1.5, 7 mm long |
|---|---|
| Cable diameter | 5 to 10 mm |
| Width across flats | 20 mm |
| Torque | 9 Nm |
| Material | brass, nickel-plated, seal CR/NBR |
| Operating temperature | -40 °C to +100 °C |
Product details
The Rittal 2411.811 is a nickel-plated brass cable gland with an M16 x 1.5 thread for cables 5 to 10 mm in diameter, supplied in a pack of 15. It seals the cable where it passes through an enclosure wall or gland plate.
Key features
- M16 x 1.5 thread, 7 mm long
- For cable diameters 5 to 10 mm
- Nickel-plated brass with CR/NBR seal
- IP 68 (5 bar, 30 min)
- Operating temperature -40 °C to +100 °C
Typical applications
The M16 size suits small control, instrument and signal cables. Brass suits jobs where a metal gland is specified, and its operating range reaches -40 °C, against -30 °C for the polyamide version. For a lighter, non-metallic gland with the same thread, see Rittal 2411.611.
Compliance
IP 68 to IEC 60529 (5 bar, 30 min) and UL 50E Type 4X. Ratings assume a cable within the stated diameter range and correct installation.
What it fits: Rittal lists it as an accessory for 73 AX compact enclosures: 39 sheet steel, 20 stainless steel and 14 GRP. It needs an M16 x 1.5 entry, such as an M16 knockout in an AX gland plate; check the 7 mm thread length against the wall or plate thickness.
Add a pack to your cart, or ask us about project quantities.