Trade only · Free delivery over £100 ex VAT
Product image coming soon

Terasaki 000959 Shunt Trip 100-120V DC, for TemBreak 2 MCCBs up to 400A

Brand:
Terasaki
Part number:
000959

Shunt trip with a 100-120 V DC coil for tripping TemBreak 2 MCCBs on the 160 A, 250 A and 400 A frames from a 110 V DC battery. Terasaki part number 000959.

  • 100-120 V DC coil for 110 V DC batteries
  • Trips even when the AC supply is down
  • TemBreak 2 160 A, 250 A and 400 A frames
  • Shunt trip or UVR per breaker, not both
£84.41 ex VAT£101.29 inc VAT

Available to order

Datasheet (PDF)Opens in a new tabBuild a board with this partConfigure a complete Terasaki Resilience panel board online: incomer, outgoing MCCBs, surge and metering, with a drawing and parts list.

UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 3-5 working days.

Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.

Project quantities or a lead time to check? Request a quote

Specifications

Electrical

Coil voltage100-120 V DC

Fit

Fits deviceTerasaki S160-NF, Terasaki S160-NJ, Terasaki S160-GJ, Terasaki S250-NJ, Terasaki S250-GJ, Terasaki S250-NE, Terasaki S250-GE, Terasaki S400-NN, Terasaki S400-NJ, Terasaki S400-NE
Fits MCCB frame160 A, 250 A, 400 A
Panelboard rangeResilience Standard, Resilience Plus
What does this mean?

Incomer and outgoing ways in one wall-mounted board. 250 A or 400 A busbars, 4 to 18 outgoing ways, outgoing MCCBs up to 125 A, Form 3b Type 2, doors included. Modular: a separate incomer housing beside the panel board, with add-on enclosures and cableways. 400 A or 800 A busbars, 6 to 18 outgoing ways, outgoing MCCBs up to 250 A (400 A on the twin board), Form 3a or 3b Type 2, doors optional.

Identification

BrandTerasaki
Part number000959
RangeTerasaki TemBreak2
TypeShunt trip

More technical data

Typeshunt trip, internal
Coil100-120 V DC
Actiontrips the breaker when the coil is energised
Breaker frames160 A, 250 A and 400 A TemBreak 2
Not withan under-voltage release
Suppliedone shunt trip with fitting instructions

Product details

The Terasaki 000959 shunt trip carries a 100-120 V DC coil for tripping TemBreak 2 MCCBs from a 110 V DC battery supply, a common arrangement in switchrooms and substations. With the trip energy coming from the battery, the breaker can still be tripped remotely while the AC supply is down.

Key features

  • 100-120 V DC coil for 110 V DC tripping batteries
  • Remote tripping stays available from the battery during an AC outage
  • Fits internally in the trip-coil position of 160 A, 250 A and 400 A frame breakers
  • Cannot be combined with an under-voltage release in the same breaker
  • Accessory screw terminals, or an optional terminal block that clips to the breaker

Typical applications

Trip commands from protection relays in substations and LV switchrooms with 110 V DC auxiliary supplies, intertripping between breakers, and emergency shutdown circuits on industrial sites that run DC control systems.

For TemBreak 2 S160-NF, S160-NJ and S160-GJ (160 A frame), S250-NJ, S250-GJ, S250-NE and S250-GE (250 A frame), and S400-NJ, S400-NE and the S400-NN switch-disconnector (400 A frame). For a 110 V AC control supply, the AC version is 000904.

Add it to your cart, or contact us if your DC system voltage falls outside this band.