Terasaki 000942 Shunt Trip 48V DC, for TemBreak 2 MCCBs up to 400A
- Brand:
- Terasaki
- Part number:
- 000942
Shunt trip with a 48 V DC coil for remote tripping of TemBreak 2 MCCBs on the 160 A, 250 A and 400 A frames. Terasaki part number 000942.
- 48 V DC coil
- For telecoms and battery-backed DC trip supplies
- TemBreak 2 160 A, 250 A and 400 A frames
- Internal, clicks into the breaker
Available to order
UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 3-5 working days.
Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.
Project quantities or a lead time to check? Request a quote
Specifications
Electrical
| Coil voltage | 48 V DC |
|---|
Fit
| Fits device | Terasaki S160-NF, Terasaki S160-NJ, Terasaki S160-GJ, Terasaki S250-NJ, Terasaki S250-GJ, Terasaki S250-NE, Terasaki S250-GE, Terasaki S400-NN, Terasaki S400-NJ, Terasaki S400-NE |
|---|---|
| Fits MCCB frame | 160 A, 250 A, 400 A |
| Panelboard range | Resilience Standard, Resilience PlusWhat does this mean?Incomer and outgoing ways in one wall-mounted board. 250 A or 400 A busbars, 4 to 18 outgoing ways, outgoing MCCBs up to 125 A, Form 3b Type 2, doors included. Modular: a separate incomer housing beside the panel board, with add-on enclosures and cableways. 400 A or 800 A busbars, 6 to 18 outgoing ways, outgoing MCCBs up to 250 A (400 A on the twin board), Form 3a or 3b Type 2, doors optional. |
Identification
| Brand | Terasaki |
|---|---|
| Part number | 000942 |
| Range | Terasaki TemBreak2 |
| Type | Shunt trip |
More technical data
| Type | shunt trip, internal |
|---|---|
| Coil | 48 V DC |
| Action | trips the breaker when energised |
| Breaker frames | 160 A, 250 A and 400 A TemBreak 2 |
| Not with | an under-voltage release |
| Supplied | one shunt trip with fitting instructions |
Product details
Terasaki 000942 is a TemBreak 2 shunt trip with a 48 V DC coil, for trip circuits fed from 48 V DC systems such as telecoms power plant and battery-backed control supplies. Fitted in a breaker on the 160 A, 250 A or 400 A frame, it trips the breaker remotely when the coil is energised.
Key features
- 48 V DC coil
- Remote trip from a contact or relay in the 48 V DC circuit
- Push-in internal fit under the breaker's front cover, no special tools
- Shares its position with the under-voltage release, so a breaker has one or the other
- Wire to the accessory's screw terminals or an optional clip-on side terminal block
Typical applications
Telecoms and data sites with 48 V DC plant, battery-supported control panels, and remote shutdown schemes where the tripping signal comes from a 48 V system. A battery-backed trip supply keeps remote tripping available during a mains failure, although the shunt trip itself cannot operate if that DC supply is lost.
Suits TemBreak 2 S160-NF, S160-NJ, S160-GJ, S250-NJ, S250-GJ, S250-NE, S250-GE, S400-NJ and S400-NE MCCBs and the S400-NN switch-disconnector.
Genuine Terasaki product. Add it to your cart.