Terasaki 003431 Shunt Trip 380-450V AC, for TemBreak 2 Lite 160A and 250A Frames

Brand:
Terasaki
Part number:
003431

Shunt trip with a 380-450 V AC coil for TemBreak 2 Lite 160 A and 250 A frame breakers, wired across two phases of a 400 V or 415 V supply. Terasaki part number 003431.

  • 380-450V AC coil, phase-to-phase connection
  • No neutral or control transformer needed
  • 0.0065 A peak exciting current
  • Fits 160A and 250A Lite frames
£84.29 ex VAT£101.15 inc VAT

Available to order

Datasheet (PDF)Opens in a new tabBuild a board with this partConfigure a complete Terasaki Resilience panel board online: incomer, outgoing MCCBs, surge and metering, with a drawing and parts list.

UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 3-5 working days.

Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.

Project quantities or a lead time to check? Request a quote

Specifications

Electrical

Coil voltage380-450 V AC

Fit

Fits deviceTerasaki E160-SF, Terasaki S160-SCJ, Terasaki E250-SJ, Terasaki S250-SN, Terasaki S250-SJ
Fits MCCB frame160 A, 250 A
Panelboard rangeResilience Standard, Resilience Plus
What does this mean?

Incomer and outgoing ways in one wall-mounted board. 250 A or 400 A busbars, 4 to 18 outgoing ways, outgoing MCCBs up to 125 A, Form 3b Type 2, doors included. Modular: a separate incomer housing beside the panel board, with add-on enclosures and cableways. 400 A or 800 A busbars, 6 to 18 outgoing ways, outgoing MCCBs up to 250 A (400 A on the twin board), Form 3a or 3b Type 2, doors optional.

Identification

BrandTerasaki
Part number003431
RangeTerasaki TemBreak2 Lite
TypeShunt trip

More technical data

Permissible voltage85-110 % of rated
Peak exciting current0.0065 A
TerminalsC1, C2
Mountinginternal accessory, trip-coil position

Product details

The Terasaki 003431 shunt trip has a 380-450 V AC coil, so a TemBreak 2 Lite breaker on the 160 A or 250 A frame can be tripped from a phase-to-phase voltage. Wired across two lines of a 400 V or 415 V supply, it needs no neutral and no control transformer.

Key features

  • Coil rated 380-450 V AC for line-to-line connection
  • Lowest coil current of the AC shunt trips: 0.0065 A peak
  • Continuous-rated coil, no anti-burn switch
  • Contacts generally begin to part within 30 ms of rated voltage reaching the coil
  • One trip-coil position per breaker: fit this or an under-voltage release

Typical applications

Three-phase installations where no neutral is brought to the panel, such as motor, pump and compressor feeders, and boards where a 400 V tripping supply is simpler than adding a control transformer. Because a shunt trip only works with voltage present, take its supply from a point that stays live whenever a trip may be needed.

Fits the TemBreak 2 Lite S160-SCJ (160 A frame) together with the E250-SJ, S250-SJ and S250-SN (250 A frame). Auxiliary and alarm switches can share the breaker.