Trade only · Free delivery over £100 ex VAT
Product image coming soon

Terasaki 000935 Shunt Trip 24V DC, for TemBreak 2 MCCBs up to 400A

Brand:
Terasaki
Part number:
000935

Shunt trip with a 24 V DC coil for tripping TemBreak 2 MCCBs on the 160 A, 250 A and 400 A frames from PLC, BMS or relay outputs. Terasaki part number 000935.

  • 24 V DC coil for PLC, BMS and safety relay outputs
  • No interposing relay needed
  • Fits TemBreak 2 160 A, 250 A and 400 A frames
  • Shunt trip or UVR per breaker, not both
£84.41 ex VAT£101.29 inc VAT

Available to order

Datasheet (PDF)Opens in a new tabBuild a board with this partConfigure a complete Terasaki Resilience panel board online: incomer, outgoing MCCBs, surge and metering, with a drawing and parts list.

UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 3-5 working days.

Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.

Project quantities or a lead time to check? Request a quote

Specifications

Electrical

Coil voltage24 V DC

Fit

Fits deviceTerasaki S160-NF, Terasaki S160-NJ, Terasaki S160-GJ, Terasaki S250-NJ, Terasaki S250-GJ, Terasaki S250-NE, Terasaki S250-GE, Terasaki S400-NN, Terasaki S400-NJ, Terasaki S400-NE
Fits MCCB frame160 A, 250 A, 400 A
Panelboard rangeResilience Standard, Resilience Plus
What does this mean?

Incomer and outgoing ways in one wall-mounted board. 250 A or 400 A busbars, 4 to 18 outgoing ways, outgoing MCCBs up to 125 A, Form 3b Type 2, doors included. Modular: a separate incomer housing beside the panel board, with add-on enclosures and cableways. 400 A or 800 A busbars, 6 to 18 outgoing ways, outgoing MCCBs up to 250 A (400 A on the twin board), Form 3a or 3b Type 2, doors optional.

Identification

BrandTerasaki
Part number000935
RangeTerasaki TemBreak2
TypeShunt trip

More technical data

Typeshunt trip, internal
Coil24 V DC
Triggervoltage applied to the coil
Breaker frames160 A, 250 A and 400 A TemBreak 2
Not withan under-voltage release in the same breaker
Suppliedone unit with fitting instructions

Product details

The Terasaki 000935 shunt trip has a 24 V DC coil, the control voltage used by many PLCs, BMS controllers and safety relays. Fitted in a TemBreak 2 MCCB on the 160 A, 250 A or 400 A frame, it trips the breaker on a command from those systems, with no interposing relay needed to change voltage.

Key features

  • 24 V DC coil to suit common control system voltages
  • Trips the breaker when a PLC output, relay contact or pushbutton energises the coil
  • Internal accessory in the trip-coil position, fitted after the front cover clips are lifted
  • Uses the position shared with the under-voltage release: one per breaker
  • Terminations on the accessory itself or on an optional terminal block clipped to the breaker

Typical applications

Automated shutdown of distribution circuits from a PLC or BMS, 24 V DC fire alarm interface outputs, emergency stop systems built on 24 V safety relays, and load shedding when a generator is carrying the site. A shunt trip needs power to act, so where the breaker must trip if the 24 V supply fails, specify an under-voltage release instead.

Compatible TemBreak 2 devices: S160-NF, S160-NJ and S160-GJ; S250-NJ, S250-GJ, S250-NE and S250-GE; S400-NJ, S400-NE and the S400-NN switch-disconnector, including those in Resilience panel boards.

Add it to your cart, or ask us to check the coil voltage against your control system.