Trade only · Free delivery over £100 ex VAT
Product image coming soon

Terasaki 003547 Under-Voltage Release 100-120V AC, for TemBreak 2 Lite 160A and 250A Frames

Brand:
Terasaki
Part number:
003547

Instantaneous under-voltage release with a 100-120 V AC coil for TemBreak 2 Lite 160 A and 250 A frame breakers; trips the breaker when its coil voltage is lost. Terasaki part number 003547.

  • 100-120V AC coil, 1.4 VA
  • Trips on loss of coil voltage
  • Instantaneous, no time delay
  • Fits 160A and 250A Lite frames
£105.38 ex VAT£126.46 inc VAT

Available to order

Datasheet (PDF)Opens in a new tabBuild a board with this partConfigure a complete Terasaki Resilience panel board online: incomer, outgoing MCCBs, surge and metering, with a drawing and parts list.

UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 3-5 working days.

Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.

Project quantities or a lead time to check? Request a quote

Specifications

Electrical

Coil voltage100-120 V AC

Fit

Fits deviceTerasaki E160-SF, Terasaki S160-SCJ, Terasaki E250-SJ, Terasaki S250-SN, Terasaki S250-SJ
Fits MCCB frame160 A, 250 A
Panelboard rangeResilience Standard, Resilience Plus
What does this mean?

Incomer and outgoing ways in one wall-mounted board. 250 A or 400 A busbars, 4 to 18 outgoing ways, outgoing MCCBs up to 125 A, Form 3b Type 2, doors included. Modular: a separate incomer housing beside the panel board, with add-on enclosures and cableways. 400 A or 800 A busbars, 6 to 18 outgoing ways, outgoing MCCBs up to 250 A (400 A on the twin board), Form 3a or 3b Type 2, doors optional.

Identification

BrandTerasaki
Part number003547
RangeTerasaki TemBreak2 Lite
TypeUnder-voltage release

More technical data

Power supply capacity1.4 VA
Operationinstantaneous
Mountinginternal, trip-coil position

Product details

The Terasaki 003547 under-voltage release (UVT) lets a TemBreak 2 Lite breaker on the 160 A or 250 A frame stay closed only while its 100-120 V AC coil is energised. If that voltage disappears, the breaker trips. Wired into a 110 V AC control circuit, it turns any break in that circuit into a trip, which makes the arrangement fail-safe.

Key features

  • Coil rated 100-120 V AC, drawing 1.4 VA
  • Instantaneous type, without a time delay
  • Trips the breaker on loss of coil voltage, including a broken wire in the control circuit
  • Uses the breaker's trip-coil position: fit an under-voltage release or a shunt trip, not both
  • Auxiliary and alarm switches can be fitted in the same breaker

Typical applications

Emergency stop circuits on 110 V AC control transformers, with the stop buttons' normally closed contacts in series with the coil; machine and plant supplies that must not come back on by themselves after an outage; and interlocks where opening a guard or door contact should trip the supply.

Fits the TemBreak 2 Lite S160-SCJ (160 A frame) and E250-SJ, S250-SJ and S250-SN (250 A frame). Where brief dips should be ridden through, Terasaki's AC time-delay releases (500 ± 300 ms, using a separate controller that mounts to the right of the breaker) are different parts.

Add it to your cart, or ask us about the time-delay version.