Trade only · Free delivery over £100 ex VAT
Product image coming soon

Terasaki 001246 Under-Voltage Release 100-120V DC, for TemBreak 2 MCCBs up to 400A

Brand:
Terasaki
Part number:
001246

Under-voltage release with a 100-120 V DC coil for TemBreak 2 MCCBs on the 160 A, 250 A and 400 A frames on 110 V DC battery systems. Terasaki part number 001246.

  • 100-120 V DC coil for 110 V DC systems
  • Trips if the DC auxiliary supply fails
  • Remote trip via a normally closed contact
  • TemBreak 2 160 A, 250 A and 400 A frames
£105.53 ex VAT£126.64 inc VAT

Available to order

Datasheet (PDF)Opens in a new tabBuild a board with this partConfigure a complete Terasaki Resilience panel board online: incomer, outgoing MCCBs, surge and metering, with a drawing and parts list.

UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 3-5 working days.

Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.

Project quantities or a lead time to check? Request a quote

Specifications

Electrical

Coil voltage100-120 V DC

Fit

Fits deviceTerasaki S160-NF, Terasaki S160-NJ, Terasaki S160-GJ, Terasaki S250-NJ, Terasaki S250-GJ, Terasaki S250-NE, Terasaki S250-GE, Terasaki S400-NN, Terasaki S400-NJ, Terasaki S400-NE
Fits MCCB frame160 A, 250 A, 400 A
Panelboard rangeResilience Standard, Resilience Plus
What does this mean?

Incomer and outgoing ways in one wall-mounted board. 250 A or 400 A busbars, 4 to 18 outgoing ways, outgoing MCCBs up to 125 A, Form 3b Type 2, doors included. Modular: a separate incomer housing beside the panel board, with add-on enclosures and cableways. 400 A or 800 A busbars, 6 to 18 outgoing ways, outgoing MCCBs up to 250 A (400 A on the twin board), Form 3a or 3b Type 2, doors optional.

Identification

BrandTerasaki
Part number001246
RangeTerasaki TemBreak2
TypeUnder-voltage release

More technical data

Typeunder-voltage release, internal
Coil100-120 V DC
Actiontrips on loss of coil voltage; holds the breaker off until it returns
Breaker frames160 A, 250 A and 400 A TemBreak 2
Not witha shunt trip in the same breaker
Suppliedone release with fitting instructions

Product details

The Terasaki 001246 under-voltage release has a 100-120 V DC coil, for TemBreak 2 MCCBs on sites that run control and protection from a 110 V DC battery. Fitted in a breaker on the 160 A, 250 A or 400 A frame, it trips the breaker if that DC supply fails or a series stop contact opens, and keeps it off until the voltage is restored.

Key features

  • 100-120 V DC coil for 110 V DC auxiliary supplies
  • Trips on loss of the DC supply; reclosing blocked until it returns
  • Remote tripping by opening a normally closed contact in series with the coil
  • Internal accessory, field-fitted under the breaker's front cover
  • Not combinable with a shunt trip, which uses the same position

Typical applications

Switchrooms and substations with 110 V DC auxiliary systems, where loss of the DC supply must take circuits off, and fail-safe tripping chains wired through station alarms, interlocks or emergency stops. For a delayed trip, add the external time-delay controller that clips to the breaker side.

Suits TemBreak 2 S160-NF, S160-NJ, S160-GJ, S250-NJ, S250-GJ, S250-NE, S250-GE, S400-NJ and S400-NE MCCBs and the S400-NN switch-disconnector. For 110 V AC control circuits, choose 001208.

Add it to your cart.