Trade only · Free delivery over £100 ex VAT
Product image coming soon

Terasaki 001215 Under-Voltage Release 200-240V AC, for TemBreak 2 MCCBs up to 400A

Brand:
Terasaki
Part number:
001215

Under-voltage release with a 200-240 V AC coil that trips TemBreak 2 MCCBs on the 160 A, 250 A and 400 A frames when a 230 V supply fails. Terasaki part number 001215.

  • 200-240 V AC coil for 230 V supplies
  • Stops plant restarting after a supply failure
  • Remote trip via a normally closed contact
  • TemBreak 2 160 A, 250 A and 400 A frames
£105.53 ex VAT£126.64 inc VAT

Available to order

Datasheet (PDF)Opens in a new tabBuild a board with this partConfigure a complete Terasaki Resilience panel board online: incomer, outgoing MCCBs, surge and metering, with a drawing and parts list.

UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 3-5 working days.

Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.

Project quantities or a lead time to check? Request a quote

Specifications

Electrical

Coil voltage200-240 V AC

Fit

Fits deviceTerasaki S160-NF, Terasaki S160-NJ, Terasaki S160-GJ, Terasaki S250-NJ, Terasaki S250-GJ, Terasaki S250-NE, Terasaki S250-GE, Terasaki S400-NN, Terasaki S400-NJ, Terasaki S400-NE
Fits MCCB frame160 A, 250 A, 400 A
Panelboard rangeResilience Standard, Resilience Plus
What does this mean?

Incomer and outgoing ways in one wall-mounted board. 250 A or 400 A busbars, 4 to 18 outgoing ways, outgoing MCCBs up to 125 A, Form 3b Type 2, doors included. Modular: a separate incomer housing beside the panel board, with add-on enclosures and cableways. 400 A or 800 A busbars, 6 to 18 outgoing ways, outgoing MCCBs up to 250 A (400 A on the twin board), Form 3a or 3b Type 2, doors optional.

Identification

BrandTerasaki
Part number001215
RangeTerasaki TemBreak2
TypeUnder-voltage release

More technical data

Typeunder-voltage release, internal
Coil200-240 V AC
Actiontrips on loss of coil voltage; reclosing blocked until it returns
Breaker frames160 A, 250 A and 400 A TemBreak 2
Not witha shunt trip in the same breaker
Suppliedone release, individually packed

Product details

Terasaki 001215 is an under-voltage release with a 200-240 V AC coil for TemBreak 2 MCCBs on the 160 A, 250 A and 400 A frames. Supplied at 230 V, it trips the breaker if that voltage collapses and prevents the breaker being reclosed until the supply is back, so connected equipment cannot start up again unattended.

Key features

  • 200-240 V AC coil for 230 V supplies and control circuits
  • Trips on loss of voltage and blocks reclosing until it is restored
  • A normally closed stop button or contact in series with the coil supply gives remote tripping
  • Fits in the breaker's trip-coil position: unclip the front cover, push the release in until it clicks
  • Cannot be fitted alongside a shunt trip, which uses the same position

Typical applications

Loss-of-supply protection on circuits feeding motors, pumps and machine tools that must not restart by themselves, emergency stop circuits wired at 230 V, and schemes that disconnect loads when a monitored 230 V supply fails. A time-delayed trip needs the external TemBreak 2 time-delay controller that clips to the breaker side.

Compatible with TemBreak 2 S160-NF, S160-NJ and S160-GJ (160 A frame), S250-NJ, S250-GJ, S250-NE and S250-GE (250 A frame), S400-NJ and S400-NE, and the S400-NN switch-disconnector (400 A frame).

Genuine Terasaki product. Add it to your cart.