Terasaki 001222 Under-Voltage Release 380-450V AC, for TemBreak 2 MCCBs up to 400A
- Brand:
- Terasaki
- Part number:
- 001222
Under-voltage release with a 380-450 V AC coil, connected line to line, for TemBreak 2 MCCBs on the 160 A, 250 A and 400 A frames. Terasaki part number 001222.
- 380-450 V AC coil, wired line to line
- Trips on loss of line voltage
- No neutral needed at the breaker
- TemBreak 2 160 A, 250 A and 400 A frames
Available to order
UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 3-5 working days.
Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.
Project quantities or a lead time to check? Request a quote
Specifications
Electrical
| Coil voltage | 380-450 V AC |
|---|
Fit
| Fits device | Terasaki S160-NF, Terasaki S160-NJ, Terasaki S160-GJ, Terasaki S250-NJ, Terasaki S250-GJ, Terasaki S250-NE, Terasaki S250-GE, Terasaki S400-NN, Terasaki S400-NJ, Terasaki S400-NE |
|---|---|
| Fits MCCB frame | 160 A, 250 A, 400 A |
| Panelboard range | Resilience Standard, Resilience PlusWhat does this mean?Incomer and outgoing ways in one wall-mounted board. 250 A or 400 A busbars, 4 to 18 outgoing ways, outgoing MCCBs up to 125 A, Form 3b Type 2, doors included. Modular: a separate incomer housing beside the panel board, with add-on enclosures and cableways. 400 A or 800 A busbars, 6 to 18 outgoing ways, outgoing MCCBs up to 250 A (400 A on the twin board), Form 3a or 3b Type 2, doors optional. |
Identification
| Brand | Terasaki |
|---|---|
| Part number | 001222 |
| Range | Terasaki TemBreak2 |
| Type | Under-voltage release |
More technical data
| Type | under-voltage release, internal |
|---|---|
| Coil | 380-450 V AC |
| Typical connection | across two phases at 400/415 V |
| Breaker frames | 160 A, 250 A and 400 A TemBreak 2 |
| Not with | a shunt trip |
| Supplied | one release with fitting instructions |
Product details
The Terasaki 001222 under-voltage release has a 380-450 V AC coil, so it can be connected across two phases of a 400/415 V supply with no neutral needed. Fitted in a TemBreak 2 MCCB on the 160 A, 250 A or 400 A frame, it trips the breaker when that line voltage is lost and holds it off until the voltage returns.
Key features
- 380-450 V AC coil, connected line to line on 400/415 V systems
- Trips on loss of the monitored voltage; no neutral required
- Remote tripping: wire a stop pushbutton or normally closed contact into the coil circuit
- Internal, field-fitted accessory that clicks into the trip-coil position
- Shares its position with the shunt trip, so a breaker takes one or the other
Typical applications
Three-phase motor and pump distribution where plant must stay off after a supply failure until someone resets it, panels with no neutral at the breaker, and fail-safe stop circuits wired at 400 V. Check that any stop button or relay contact in series with the coil is rated for line voltage. Delayed tripping needs the external time-delay controller that clips to the breaker side.
For TemBreak 2 S160-NF, S160-NJ, S160-GJ, S250-NJ, S250-GJ, S250-NE, S250-GE, S400-NJ and S400-NE MCCBs and the S400-NN switch-disconnector.
Add it to your cart, or ask us to check the right release for your supply.