Europa ATS-CON802PME 80A 2-Pole Single Phase Automatic Transfer Switch, 230V
- Brand:
- Europa Components
- Part number:
- ATS-CON802PME
- EAN:
- 5056551200593
An 80 A two-pole single-phase automatic transfer switch for 230 V installations. It transfers the load to a standby generator on mains failure and back again unattended.
- 80 A AC1 single-phase automatic transfer
- Two-pole 230 V operation
- Cable capacity to 25 sq mm
- Unattended generator start and mains return
- Built to BS EN IEC 60947-6-1
1 in stock
UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 2-3 working days.
Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.
Project quantities or a lead time to check? Request a quote
Specifications
Electrical
| Rated current | 80 A |
|---|---|
| Poles / neutral | 2 pole |
| Neutral | No neutral |
| Supply | Single phase |
| Utilisation category | AC-1 |
| Voltage | 230 V |
Protection
| Door interlock | No |
|---|
Construction
| Enclosure material | Sheet steel |
|---|
Identification
| Brand | Europa Components |
|---|---|
| Part number | ATS-CON802PME |
| EAN | 5056551200593 |
| Range | Europa ATS |
| Type | Automatic transfer switch |
More technical data
| Rated operational current | 80 A, AC1 |
|---|---|
| Poles | 2, single phase 230 V |
| Maximum cable size | 25 sq mm |
| Switching | contactor-based, mains and generator sources |
| Control | mains failure relay plus delay-on-start, changeover, mains return and cool-down timers |
Product details
The Europa ATS-CON802PME is an 80 A single-phase automatic transfer switch for 230 V installations that cannot tolerate downtime. It uses two contactors, a mains failure relay and a set of adjustable timers to detect a supply problem, start the generator, transfer the load and then hand it back to the mains once the incomer has been healthy long enough to trust.
Key features
- 80 A operational current in category AC1, line and neutral switched
- Terminals take conductors up to 25 sq mm
- Mains failure relay with adjustable thresholds, hysteresis and delay
- Changeover timer set to cover the generator start-up and run-up period
- Cool-down timer keeps the set running unloaded before it is stopped
Typical applications
An 80 A single-phase ATS is the usual fit for larger rural properties, small care and residential homes, holiday parks, telecoms and broadcast sites, and light commercial premises with refrigeration or process loads. It is also specified on water and sewage pumping kiosks where a failed pump means an overflow rather than an inconvenience.
Compliance
Europa lists this automatic transfer switch to BS, EN and IEC 60947-6-1, the standard covering low-voltage multiple-function switching equipment such as transfer switching equipment. The control devices are DIN rail mounted to EN and IEC 60715.
Order the ATS-CON802PME online for fast UK dispatch, or contact our technical team for help coordinating the ATS with your generator control panel.