Europa ATS-CON1254PME 125A 4-Pole Three Phase Automatic Transfer Switch, 415V
- Brand:
- Europa Components
- Part number:
- ATS-CON1254PME
- EAN:
- 5056551200548
A 125 A four-pole three-phase automatic transfer switch for 415 V supplies. It is the largest of the contactor-based 40 to 125 A units in the Europa ATS range.
- 125 A AC1 three-phase automatic transfer
- Four-pole 415 V operation
- Cable capacity to 50 sq mm
- Full automatic transfer and return sequence
- Built to BS EN IEC 60947-6-1
Out of stock
UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 2-3 working days.
Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.
Project quantities or a lead time to check? Request a quote
Specifications
Electrical
| Rated current | 125 A |
|---|---|
| Poles / neutral | 4 pole |
| Neutral | Switched neutral |
| Supply | Three phase |
| Utilisation category | AC-1 |
| Voltage | 400/415 V |
Protection
| Door interlock | No |
|---|
Construction
| Enclosure material | Sheet steel |
|---|
Identification
| Brand | Europa Components |
|---|---|
| Part number | ATS-CON1254PME |
| EAN | 5056551200548 |
| Range | Europa ATS |
| Type | Automatic transfer switch |
More technical data
| Rated operational current | 125 A, AC1 |
|---|---|
| Poles | 4, three phase 415 V |
| Maximum cable size | 50 sq mm |
| Switching | contactor-based, mains and generator sources |
| Control | mains failure relay plus delay-on-start, changeover, mains return and cool-down timers |
Product details
The Europa ATS-CON1254PME is a 125 A four-pole automatic transfer switch for 415 V three-phase supplies, and the top of Europa's 40 to 125 A contactor-based ATS range. With terminals accepting up to 50 sq mm it can be fitted at a building intake, transferring the whole load to a standby generator and back again with no one present.
Key features
- 125 A operational current in category AC1 across four poles at 415 V
- Terminals take conductors up to 50 sq mm for building intake duty
- Mains failure relay with adjustable thresholds, hysteresis and time delay
- Delay-on-start and changeover timers matched to generator run-up
- Mains return and cool-down timers for a controlled handback and shutdown
Typical applications
At 125 A the three-phase ATS is a building or site transfer point: hospitals, clinics and care homes, data and comms facilities, water and wastewater works, cold storage and food manufacturing, and commercial premises where life safety systems and refrigeration must not stop.
Compliance
Europa lists this automatic transfer switch to BS, EN and IEC 60947-6-1, the standard covering low-voltage multiple-function switching equipment such as transfer switching equipment. The control devices are DIN rail mounted to EN and IEC 60715.
Order the ATS-CON1254PME at trade-direct pricing with fast UK dispatch, or speak to our team about the 250 A and 400 A units for larger loads.