Europa ATS-CON602PME 60A 2-Pole Single Phase Automatic Transfer Switch, 230V
- Brand:
- Europa Components
- Part number:
- ATS-CON602PME
- EAN:
- 5056551200579
A 60 A two-pole single-phase automatic transfer switch for 230 V supplies. It monitors the mains and moves the load to a standby generator automatically, then returns it when the mains is healthy.
- 60 A AC1 single-phase automatic transfer
- Two-pole 230 V operation
- Cable capacity to 16 sq mm
- Automatic generator start and mains return
- Built to BS EN IEC 60947-6-1
1 in stock
UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 2-3 working days.
Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.
Project quantities or a lead time to check? Request a quote
Specifications
Electrical
| Rated current | 60 A |
|---|---|
| Poles / neutral | 2 pole |
| Neutral | No neutral |
| Supply | Single phase |
| Utilisation category | AC-1 |
| Voltage | 230 V |
Protection
| Door interlock | No |
|---|
Construction
| Enclosure material | Sheet steel |
|---|
Identification
| Brand | Europa Components |
|---|---|
| Part number | ATS-CON602PME |
| EAN | 5056551200579 |
| Range | Europa ATS |
| Type | Automatic transfer switch |
More technical data
| Rated operational current | 60 A, AC1 |
|---|---|
| Poles | 2, single phase 230 V |
| Maximum cable size | 16 sq mm |
| Switching | contactor-based, mains and generator sources |
| Control | mains failure relay plus delay-on-start, changeover, mains return and cool-down timers |
Product details
The Europa ATS-CON602PME is a 60 A single-phase automatic transfer switch that handles the whole mains-to-generator sequence without an operator. It monitors the 230 V incomer, starts the set when the supply falls outside the set thresholds, transfers the load once the generator is running, and reverses the process on mains return with a cool-down period before the set is stopped.
Key features
- 60 A operational current in category AC1 across two poles
- Terminals accept cable up to 16 sq mm, matching a 60 A single-phase supply
- Adjustable mains failure relay watching for both under-voltage and over-voltage
- Delay-on-start and changeover timers coordinate the generator run-up
- Mains return and cool-down timers avoid short-cycling the set on a flickering supply
Typical applications
At 60 A this ATS typically backs a whole small building: a rural guest house or pub, a veterinary or dental practice, a small data or comms room, a farm with refrigeration and milking plant, or a water booster set. It is also used where mains dips are frequent and the site cannot spare somebody to operate a changeover by hand.
Compliance
Europa lists this automatic transfer switch to BS, EN and IEC 60947-6-1, the standard covering low-voltage multiple-function switching equipment such as transfer switching equipment. The control devices are DIN rail mounted to EN and IEC 60715.
Order the ATS-CON602PME at trade-direct pricing with fast UK dispatch, or ask our team to sanity-check the rating against your generator output.