Europa ATS-CON1252PME 125A 2-Pole Single Phase Automatic Transfer Switch, 230V
- Brand:
- Europa Components
- Part number:
- ATS-CON1252PME
- EAN:
- 5056551200531
A 125 A two-pole single-phase automatic transfer switch for 230 V supplies. It is the largest single-phase unit in the Europa ATS range.
- 125 A AC1 single-phase automatic transfer
- Two-pole 230 V operation
- Cable capacity to 50 sq mm
- Full automatic transfer and return sequence
- Built to BS EN IEC 60947-6-1
1 in stock
UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 2-3 working days.
Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.
Project quantities or a lead time to check? Request a quote
Specifications
Electrical
| Rated current | 125 A |
|---|---|
| Poles / neutral | 2 pole |
| Neutral | No neutral |
| Supply | Single phase |
| Utilisation category | AC-1 |
| Voltage | 230 V |
Protection
| Door interlock | No |
|---|
Construction
| Enclosure material | Sheet steel |
|---|
Identification
| Brand | Europa Components |
|---|---|
| Part number | ATS-CON1252PME |
| EAN | 5056551200531 |
| Range | Europa ATS |
| Type | Automatic transfer switch |
More technical data
| Rated operational current | 125 A, AC1 |
|---|---|
| Poles | 2, single phase 230 V |
| Maximum cable size | 50 sq mm |
| Switching | contactor-based, mains and generator sources |
| Control | mains failure relay plus delay-on-start, changeover, mains return and cool-down timers |
Product details
The Europa ATS-CON1252PME is a 125 A single-phase automatic transfer switch and the largest two-pole unit in Europa's ATS range. It terminates cable up to 50 sq mm, so it can be fitted directly at a heavy single-phase intake, and it runs the full mains failure, generator start, transfer, return and cool-down sequence on its own.
Key features
- 125 A operational current in category AC1, line and neutral switched
- Terminals take conductors up to 50 sq mm for heavy single-phase intakes
- Mains failure relay monitoring voltage with adjustable thresholds and delay
- Delay-on-start and changeover timers tuned to the generator run-up time
- Mains return and cool-down timers for a controlled handback and shutdown
Typical applications
At 125 A the single-phase ATS covers larger rural and estate properties, small care and residential homes, veterinary practices, holiday parks and marinas, telecoms hubs and food premises with substantial refrigeration. It is the right unit where the whole single-phase load, not just an essential circuit, has to ride through an outage.
Compliance
Europa lists this automatic transfer switch to BS, EN and IEC 60947-6-1, the standard covering low-voltage multiple-function switching equipment such as transfer switching equipment. The control devices are DIN rail mounted to EN and IEC 60715.
Order the ATS-CON1252PME at trade-direct pricing with fast UK dispatch, or contact us if a three-phase unit would suit the installation better.