Trade only · Free delivery over £100 ex VAT
Product image 1

Europa ATS-CON1002PME 100A 2-Pole Single Phase Automatic Transfer Switch, 230V

Brand:
Europa Components
Part number:
ATS-CON1002PME
EAN:
5056551200517

A 100 A two-pole single-phase automatic transfer switch for 230 V supplies. It is sized to transfer a whole single-phase service to a standby generator automatically.

  • 100 A AC1 single-phase automatic transfer
  • Two-pole 230 V operation
  • Cable capacity to 35 sq mm
  • Automatic start, transfer and return
  • Built to BS EN IEC 60947-6-1
£1,011.60 ex VAT£1,213.92 inc VAT

2 in stock

Datasheet (PDF)Opens in a new tab

UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 2-3 working days.

Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.

Project quantities or a lead time to check? Request a quote

Specifications

Electrical

Rated current100 A
Poles / neutral2 pole
NeutralNo neutral
SupplySingle phase
Utilisation categoryAC-1
Voltage230 V

Protection

Door interlockNo

Construction

Enclosure materialSheet steel

Identification

BrandEuropa Components
Part numberATS-CON1002PME
EAN5056551200517
RangeEuropa ATS
TypeAutomatic transfer switch

More technical data

Rated operational current100 A, AC1
Poles2, single phase 230 V
Maximum cable size35 sq mm
Switchingcontactor-based, mains and generator sources
Controlmains failure relay plus delay-on-start, changeover, mains return and cool-down timers

Product details

The Europa ATS-CON1002PME is a 100 A single-phase automatic transfer switch, sized to move an entire 230 V service across to a standby generator without an operator. It is the rating most often matched to a 100 A domestic or small commercial cut-out, and the adjustable timers let the sequence be tuned to the run-up characteristics of the particular set.

Key features

  • 100 A operational current in category AC1 across two poles
  • Terminals accept conductors up to 35 sq mm, suiting a 100 A single-phase service
  • Mains failure relay with adjustable over-voltage, under-voltage, hysteresis and delay
  • Delay-on-start timer prevents the generator being called on a momentary dip
  • Mains return and cool-down timers manage the handback and shutdown sequence

Typical applications

A 100 A single-phase ATS is specified for rural homes and farms on exposed networks, small healthcare and residential care premises, communications and data cabinets, cold stores, and pumping stations where an outage has immediate consequences. It also suits sites that have outgrown a manual changeover and want the transfer to happen while nobody is there.

Compliance

Europa lists this automatic transfer switch to BS, EN and IEC 60947-6-1, the standard covering low-voltage multiple-function switching equipment such as transfer switching equipment. The control devices are DIN rail mounted to EN and IEC 60715.

Order the ATS-CON1002PME for fast UK dispatch, or speak to our technical team about generator start contacts and setting the changeover timer.