Europa ATS-CON604PME 60A 4-Pole Three Phase Automatic Transfer Switch, 415V
- Brand:
- Europa Components
- Part number:
- ATS-CON604PME
- EAN:
- 5056551200586
A 60 A four-pole three-phase automatic transfer switch for 415 V supplies. It transfers the load to a standby generator on mains failure and returns it automatically.
- 60 A AC1 three-phase automatic transfer
- Four-pole 415 V operation
- Cable capacity to 16 sq mm
- Automatic generator start and mains return
- Built to BS EN IEC 60947-6-1
3 in stock
UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 2-3 working days.
Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.
Project quantities or a lead time to check? Request a quote
Specifications
Electrical
| Rated current | 60 A |
|---|---|
| Poles / neutral | 4 pole |
| Neutral | Switched neutral |
| Supply | Three phase |
| Utilisation category | AC-1 |
| Voltage | 400/415 V |
Protection
| Door interlock | No |
|---|
Construction
| Enclosure material | Sheet steel |
|---|
Identification
| Brand | Europa Components |
|---|---|
| Part number | ATS-CON604PME |
| EAN | 5056551200586 |
| Range | Europa ATS |
| Type | Automatic transfer switch |
More technical data
| Rated operational current | 60 A, AC1 |
|---|---|
| Poles | 4, three phase 415 V |
| Maximum cable size | 16 sq mm |
| Switching | contactor-based, mains and generator sources |
| Control | mains failure relay plus delay-on-start, changeover, mains return and cool-down timers |
Product details
The Europa ATS-CON604PME is a 60 A four-pole automatic transfer switch for 415 V three-phase supplies. It carries the load on one of two contactors, with a mains failure relay deciding when to change over and a set of adjustable timers making sure the generator is up to speed before the transfer and properly cooled before it stops.
Key features
- 60 A operational current in category AC1 on four poles at 415 V
- Terminals accept conductors up to 16 sq mm
- Mains failure relay monitoring the incoming supply against adjustable thresholds
- Changeover timer set to cover the generator start and run-up period
- Cool-down timer runs the set unloaded before the stop signal is given
Typical applications
A 60 A three-phase ATS typically backs a plant area or a small building: water and effluent pumping, cold rooms and chillers, bakery and food process lines, comms rooms, and workshop supplies feeding CNC or extraction plant that must not stop mid-cycle.
Compliance
Europa lists this automatic transfer switch to BS, EN and IEC 60947-6-1, the standard covering low-voltage multiple-function switching equipment such as transfer switching equipment. The control devices are DIN rail mounted to EN and IEC 60715.
Order the ATS-CON604PME at trade-direct pricing with fast UK dispatch, or contact our team to check the rating against your connected load.