Trade only · Free delivery over £100 ex VAT
Product image 1

Europa ATS-CON604PME 60A 4-Pole Three Phase Automatic Transfer Switch, 415V

Brand:
Europa Components
Part number:
ATS-CON604PME
EAN:
5056551200586

A 60 A four-pole three-phase automatic transfer switch for 415 V supplies. It transfers the load to a standby generator on mains failure and returns it automatically.

  • 60 A AC1 three-phase automatic transfer
  • Four-pole 415 V operation
  • Cable capacity to 16 sq mm
  • Automatic generator start and mains return
  • Built to BS EN IEC 60947-6-1
£1,024.62 ex VAT£1,229.54 inc VAT

3 in stock

Datasheet (PDF)Opens in a new tab

UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 2-3 working days.

Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.

Project quantities or a lead time to check? Request a quote

Specifications

Electrical

Rated current60 A
Poles / neutral4 pole
NeutralSwitched neutral
SupplyThree phase
Utilisation categoryAC-1
Voltage400/415 V

Protection

Door interlockNo

Construction

Enclosure materialSheet steel

Identification

BrandEuropa Components
Part numberATS-CON604PME
EAN5056551200586
RangeEuropa ATS
TypeAutomatic transfer switch

More technical data

Rated operational current60 A, AC1
Poles4, three phase 415 V
Maximum cable size16 sq mm
Switchingcontactor-based, mains and generator sources
Controlmains failure relay plus delay-on-start, changeover, mains return and cool-down timers

Product details

The Europa ATS-CON604PME is a 60 A four-pole automatic transfer switch for 415 V three-phase supplies. It carries the load on one of two contactors, with a mains failure relay deciding when to change over and a set of adjustable timers making sure the generator is up to speed before the transfer and properly cooled before it stops.

Key features

  • 60 A operational current in category AC1 on four poles at 415 V
  • Terminals accept conductors up to 16 sq mm
  • Mains failure relay monitoring the incoming supply against adjustable thresholds
  • Changeover timer set to cover the generator start and run-up period
  • Cool-down timer runs the set unloaded before the stop signal is given

Typical applications

A 60 A three-phase ATS typically backs a plant area or a small building: water and effluent pumping, cold rooms and chillers, bakery and food process lines, comms rooms, and workshop supplies feeding CNC or extraction plant that must not stop mid-cycle.

Compliance

Europa lists this automatic transfer switch to BS, EN and IEC 60947-6-1, the standard covering low-voltage multiple-function switching equipment such as transfer switching equipment. The control devices are DIN rail mounted to EN and IEC 60715.

Order the ATS-CON604PME at trade-direct pricing with fast UK dispatch, or contact our team to check the rating against your connected load.