Mersen Surge-Trap STPT12-12K275V-2PGM Type 1+2 Surge Protection Device, 2 Pole TT/TN
- Brand:
- Mersen
- Part number:
- 83120115
- EAN:
- 8435297849124
Two-pole pluggable combined Type 1+2 surge arrester for single-phase TT systems, rated Iimp 12.5kA per phase with a remote end-of-life contact and replaceable cartridges.
- Combined Type 1+2 protection
- Single-phase TT, 2 pole
- Iimp 12.5kA, Imax 50kA, Up 1.3kV
- Remote end-of-life contact
- Plug-in coded cartridges
77 in stock
UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 2-3 working days.
Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.
Project quantities or a lead time to check? Request a quote
Specifications
Electrical
| Supply | Single phase |
|---|---|
| Earthing system | TT, TN-S, TN-C-S (PME) |
| Earthing system (as supplied) | TT/TN |
| Remote signalling contact | Yes |
| Application | Mains AC |
Protection
| SPD type | Type 1+2 |
|---|---|
| Lightning impulse current (Iimp per pole) | 12.5 kA |
| Max discharge current (Imax) | 50 kA |
| Voltage protection level (Up) | 1.3 kV |
Dimensions
| DIN rail width | 2 modules |
|---|
Construction
| Replaceable protection module | Yes |
|---|
Fit
| Mounting | DIN rail |
|---|
Identification
| Brand | Mersen |
|---|---|
| Part number | 83120115 |
| EAN | 8435297849124 |
| Range | Mersen Surge-Trap STPT12 |
More technical data
| Manufacturer | Mersen (Surge-Trap STPT12, catalogue STPT12-12K275V-2PGM) |
|---|---|
| SPD class | Type 1+2 / Class I+II to IEC 61643-11 and EN 61643-11 |
| System | TT, single phase plus neutral; Un 230 VAC; Uc 275V |
| Lightning impulse current Iimp (10/350) | 12.5kA L-N, 25kA N-PE |
| Max discharge current Imax (8/20) | 50kA; nominal discharge current In: 20kA |
| Voltage protection level Up at In | 1.3kV (L-N), 1.5kV (N-PE) |
| Remote contact | yes; cartridges SP12-12K275V (L-N) and SP12-25K-N (N-PE) |
- Back-up fuse 200A gG, Icc 25kA, IP20, PA66 V-0 body, -40 to +80C
Product details
Mersen's Surge-Trap STPT12 is the pluggable combined arrester for the incoming position, and this two-pole version is configured for single-phase TT installations. It discharges a 12.5kA lightning impulse current per phase, holds the protection level to 1.3kV line to neutral, and reports its own end of life through a remote contact.
Key features
- Combined Type 1+2 / Class I+II protection for the incoming supply position
- Two-pole TT configuration with a dedicated 25kA neutral-to-earth cartridge
- Plug-in cartridges are mechanically coded, so the wrong one cannot be fitted
- Visual and remote end-of-life indicators for local and supervised monitoring
- Reversible chassis allows cable entry from above or below to suit the board
Typical applications
The STPT12 range is aimed at incoming power supply panels and areas exposed to the weather, particularly where a building has an external lightning protection system. Typical single-phase TT uses are rural and agricultural supplies, pumping and telemetry stations, outbuildings and site cabins on an electrode earth, telecoms enclosures and LV metering positions.
Compliance
Tested to IEC 61643-11 and EN 61643-11 as a Type 1+2 / Class I+II device, with a PA66 CT1 V-0 body and IP20 protection for enclosure mounting. BS 7671 requires the risk from transient overvoltages to be assessed, with Type 1 protection used where partial lightning current may enter the installation.
Order today for fast UK dispatch on genuine Mersen surge protection at trade-direct prices.