Trade only · Free delivery over £100 ex VAT
Product image 1

DEHN DEHNshield DSH TN 255 Combined Type 1+2 Surge Protection Device, 2 Module Single Phase TN

Brand:
DEHN
Part number:
941200
EAN:
4013364154988

Compact two-module Type 1+2 arrester for TN installations at 230V single phase, prewired and able to protect terminal equipment directly.

  • Compact combined Type 1+2 protection
  • Single-phase TN systems
  • Itotal 25kA, Iimp 12.5kA, UP 1.5kV
  • Only two DIN modules
  • Protects terminal equipment
£375.00 ex VAT£450.00 inc VAT

Out of stock

Datasheet (PDF)Opens in a new tab

UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 2-3 working days.

Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.

Project quantities or a lead time to check? Request a quote

Specifications

Electrical

SupplySingle phase
Earthing systemTN-S, TN-C-S (PME)
Earthing system (as supplied)TN
Remote signalling contactNo
ApplicationMains AC

Protection

SPD typeType 1+2
Lightning impulse current (Iimp per pole)12.5 kA
Total discharge current (Itotal)25 kA
Voltage protection level (Up)1.5 kV

Dimensions

DIN rail width2 modules

Fit

MountingDIN rail

Identification

BrandDEHN
Part number941200
EAN4013364154988
RangeDEHNshield

More technical data

ManufacturerDEHN (DEHNshield, type DSH TN 255)
SPD classType 1 + Type 2 / Class I + Class II to EN 61643-11 / IEC 61643-11
Nominal a.c. voltage (UN)230V, 50/60Hz; UC 255V
Lightning impulse current L+N-PE Itotal (10/350)25kA; Iimp 12.5kA per conductor
Nominal discharge current In (8/20)12.5kA (L/N-PE), 25kA (L+N-PE)
Voltage protection level UP1.5kV; response time 100ns
Follow current extinguishing capability Ifi25kArms
EAN as supplied4013364154988
  • Max mains-side overcurrent protection 160A gL/gG; width 2 modules, IP20, -40 to +80C

Product details

The DSH TN 255 is DEHNshield configured for single-phase TN systems. It packs combined Type 1 and Type 2 duty into two DIN modules, carries 12.5kA of lightning impulse current per conductor and holds the protection level at 1.5kV - enough to protect terminal equipment directly on a simple installation.

Key features

  • Combined Type 1 and Type 2 protection for single-phase TN systems in two modules
  • Prewired spark-gap construction, ready to land on incoming conductors
  • Lightning impulse current Iimp of 12.5kA per conductor, 25kA total L+N-PE
  • Follow current limitation will not trip a 32A gL/gG fuse up to 25kArms prospective
  • Energy coordinated with Type 3 equipment within 5m

Typical applications

Designed for compact, simply equipped installations on a TN supply: single-phase intake positions in domestic and small commercial property, flats and apartment landlord supplies, small workshops and retail units, and packaged equipment cabinets. It is the sensible Type 1 choice where a full four-module arrester cannot be accommodated.

Compliance

Tested as a Type 1 + Type 2 / Class I + Class II device to EN 61643-11 and IEC 61643-11, with KEMA, VDE and UL approvals, a UL 94 V-0 enclosure and IP20 protection. BS 7671 requires transient overvoltage risk to be assessed, with Type 1 protection where partial lightning current may enter the installation.

Order today for fast UK dispatch on genuine DEHN combined arresters at trade-direct prices.