Trade only · Free delivery over £100 ex VAT
Product image 1

Mersen Surge-Trap STPT12-12K275V-2PM Type 1+2 Surge Protection Device, 2 Pole TN-S

Brand:
Mersen
Part number:
83120121
EAN:
8435297849131

Two-pole pluggable combined Type 1+2 surge arrester for single-phase TN-S systems, with 12.5kA lightning impulse rating on both poles and a remote end-of-life contact.

  • Combined Type 1+2 protection
  • Single-phase TN-S, 2 pole
  • Iimp 12.5kA, Imax 50kA, Up 1.3kV
  • Remote end-of-life contact
  • Plug-in coded cartridges
£202.40 ex VAT£242.88 inc VAT

Out of stock

Datasheet (PDF)Opens in a new tab

UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 2-3 working days.

Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.

Project quantities or a lead time to check? Request a quote

Specifications

Electrical

SupplySingle phase
Earthing systemTN-S, TN-C-S (PME)
Earthing system (as supplied)TN
Remote signalling contactYes
ApplicationMains AC

Protection

SPD typeType 1+2
Lightning impulse current (Iimp per pole)12.5 kA
Max discharge current (Imax)50 kA
Voltage protection level (Up)1.3 kV

Dimensions

DIN rail width2 modules

Construction

Replaceable protection moduleYes

Fit

MountingDIN rail

Identification

BrandMersen
Part number83120121
EAN8435297849131
RangeMersen Surge-Trap STPT12

More technical data

ManufacturerMersen (Surge-Trap STPT12, catalogue STPT12-12K275V-2PM)
SPD classType 1+2 / Class I+II to IEC 61643-11 and EN 61643-11
SystemTN-S, single phase plus neutral; Un 230 VAC; Uc 275V
Lightning impulse current Iimp (10/350)12.5kA
Max discharge current Imax (8/20)50kA; nominal discharge current In: 20kA
Voltage protection level Up at In1.3kV
Remote contactyes; cartridge SP12-12K275V
  • Back-up fuse 200A gG, Icc 25kA, IP20, PA66 V-0 body, -40 to +80C

Product details

Configured for single-phase TN-S supplies, this Surge-Trap STPT12 arrester uses identical 275V cartridges on both poles rather than the neutral spark gap needed on a TT system. It carries 12.5kA of lightning impulse current per pole and holds the protection level to 1.3kV.

Key features

  • Combined Type 1+2 / Class I+II protection for single-phase TN-S installations
  • Two poles, both using the SP12-12K275V cartridge for 230V line-neutral duty
  • Mechanically coded plug-in cartridges prevent replacement errors
  • Visual and remote end-of-life indication built into the unit
  • Reversible chassis for cable entry from either direction

Typical applications

Fit it at incoming supply panels on TN-S installations exposed to direct lightning effects: industrial and commercial buildings with an external lightning protection system, distribution centres and warehouses, water treatment and smart grid metering positions, and telecoms or data equipment rooms fed from a dedicated single-phase supply.

Compliance

Tested to IEC 61643-11 and EN 61643-11 as a Type 1+2 / Class I+II device, with a PA66 CT1 V-0 body and IP20 protection. BS 7671 requires transient overvoltage risk to be assessed, with Type 1 protection where partial lightning current may enter the installation and coordinated Type 2 protection downstream.