DEHN DEHNvenCI DVCI 1 255 FM Type 1 Surge Protection Device with Integrated Backup Fuse
- Brand:
- DEHN
- Part number:
- 961205
- EAN:
- 4013364145115
Single-pole spark-gap Type 1 lightning current arrester with an integrated lightning-current-carrying backup fuse and a remote signalling changeover contact, in two DIN modules.
- Type 1 lightning current arrester
- Integrated backup fuse - no external fuse
- Iimp 25kA, UP 1.5kV
- Changeover contact for remote alarm
- Two DIN modules
Out of stock
UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 2-3 working days.
Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.
Project quantities or a lead time to check? Request a quote
Specifications
Electrical
| Supply | Single phase |
|---|---|
| Remote signalling contact | Yes |
| Application | Mains AC |
Protection
| SPD type | Type 1+2 |
|---|---|
| Lightning impulse current (Iimp per pole) | 25 kA |
| Voltage protection level (Up) | 1.5 kV |
Dimensions
| DIN rail width | 2 modules |
|---|
Identification
| Brand | DEHN |
|---|---|
| Part number | 961205 |
| EAN | 4013364145115 |
| Range | DEHNvenCI |
More technical data
| Manufacturer | DEHN (DEHNvenCI, type DVCI 1 255 FM) |
|---|---|
| SPD class | Type 1 / Class I to EN 61643-11 / IEC 61643-11 |
| Nominal a.c. voltage (UN) | 230V, 50/60Hz; UC 255V |
| Lightning impulse current Iimp (10/350) | 25kA; specific energy 156.25 kJ/ohms |
| Nominal discharge current In (8/20) | 25kA; voltage protection level UP: 1.5kV |
| Follow current extinguishing capability Ifi | 50kArms; response time 100ns |
| Max mains-side overcurrent protection | not required; internal backup fuse breaking capacity 100kA |
| Remote signalling | changeover contact, 250V/0.5A a.c.; width 2 modules, IP20 |
Product details
The usual headache with a Type 1 arrester at the intake is the separate backup fuse: it needs space, a fuse holder and correct selection. DEHNvenCI builds that fuse into the arrester. The DVCI 1 255 FM carries a 25kA lightning impulse current, needs no external mains-side overcurrent protection, and reports its own status through a changeover contact.
Key features
- Integrated lightning-current-carrying backup fuse - no separate mains-side fuse required
- Spark-gap technology with RADAX Flow follow current limitation for high system availability
- Iimp of 25kA (10/350) with a voltage protection level held to 1.5kV
- Remote signalling changeover contact rated 250V / 0.5A a.c.
- Follow current limitation will not trip a 20A gG fuse up to 50kArms prospective
Typical applications
This is an origin-of-installation device: main intake positions and incoming panels in buildings with an external lightning protection system, or with an overhead supply, on sites where a direct strike can put partial lightning current into the installation. It suits industrial premises, agricultural buildings, telecoms and broadcast sites, and any switchboard where there is no room for a separate 315A backup fuse arrangement.
Compliance
Tested as a Type 1 / Class I device to EN 61643-11 and IEC 61643-11, with KEMA approval, a UL 94 V-0 enclosure and IP20 protection. Energy coordination is declared with Type 2 equipment and, within 10m, with Type 3 equipment. BS 7671 requires transient overvoltage risk to be assessed, with Type 1 protection used where partial lightning current may enter the installation.
Order today for fast UK dispatch on genuine DEHN lightning current arresters at trade-direct prices.