DEHN DEHNguard DG M TT 275 Type 2 Surge Protection Device, 4 Module Three Phase TT
- Brand:
- DEHN
- Part number:
- 952310
- EAN:
- 4013364108479
Four-module Type 2 surge arrester for three-phase TT and TN-S systems, using a 3+1 circuit with an N-PE spark gap. Prewired with pluggable protection modules.
- Type 2 protection, three-phase TT and TN-S
- 3+1 circuit with N-PE spark gap
- In 20kA, Imax 40kA, UP 1.25kV
- Four DIN modules, prewired
- Pluggable protection modules
6 in stock
UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 2-3 working days.
Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.
Project quantities or a lead time to check? Request a quote
Specifications
Electrical
| Supply | Three phase |
|---|---|
| Earthing system | TT, TN-S, TN-C-S (PME) |
| Earthing system (as supplied) | TT/TN |
| Remote signalling contact | No |
| Application | Mains AC |
Protection
| SPD type | Type 2 |
|---|---|
| Nominal discharge current (In) | 20 kA |
| Max discharge current (Imax) | 40 kA |
| Voltage protection level (Up) | 1.25 kV |
Dimensions
| DIN rail width | 4 modules |
|---|
Construction
| Replaceable protection module | Yes |
|---|
Fit
| Mounting | DIN rail |
|---|
Identification
| Brand | DEHN |
|---|---|
| Part number | 952310 |
| EAN | 4013364108479 |
| Range | DEHNguard |
More technical data
| Manufacturer | DEHN (DEHNguard modular, type DG M TT 275) |
|---|---|
| SPD class | Type 2 to EN 61643-11 / Class II to IEC 61643-1 |
| Nominal a.c. voltage (UN) | 230/400V; UC 275V (L-N), 255V (N-PE) |
| Nominal discharge current In (8/20) | 20kA; max discharge current Imax: 40kA |
| Lightning impulse current N-PE (10/350) Iimp | 12kA |
| Voltage protection level UP | 1.25kV (L-N), 1.5kV (N-PE); 1kV at 5kA |
| Follow current extinguishing capability N-PE | 100Arms; max backup fuse 125A gL/gG |
- Width 4 modules (DIN 43880), IP20, 35mm DIN rail to EN 60715, -40 to +80C
Product details
Three-phase TT installations call for the 3+1 arrangement: a varistor on each line to neutral and a spark gap from neutral to earth. The DEHNguard DG M TT 275 packages that into four prewired DIN modules, carrying a 20kA nominal discharge current per phase and a 12kA lightning impulse rating on the N-PE path.
Key features
- 3+1 circuit suits three-phase TT systems as well as TN-S installations
- Prewired complete unit, ready to land on 230/400V incoming conductors
- Pluggable protection modules replaced individually, wiring left untouched
- Thermo Dynamic Control monitoring for safe disconnection of a failing varistor
- N-PE spark gap with 100Arms follow current extinguishing capability
Typical applications
Fit it at the main or sub-distribution board of three-phase installations with an electrode earth: farms and rural estates, water and wastewater pumping, quarries and outdoor process plant, telecom and broadcast compounds, and temporary building supplies. On TN-S systems the same unit covers three-phase panel boards, machinery supplies and sub-mains feeding drives, controls and IT.
Compliance
Tested as a Type 2 device to EN 61643-11 and Class II to IEC 61643-1, with KEMA, VDE, UL and VdS approvals, a UL 94 V-0 enclosure and IP20 protection. BS 7671 requires the risk from transient overvoltages to be assessed and coordinated protection provided where the consequences justify it.