DEHN DEHNguard DG TT 5 275 Compact Type 2 Surge Protection Device, 2 Module Three Phase TT/TN
- Brand:
- DEHN
- Part number:
- 900455
- EAN:
- 5056551244375
Compact three-phase Type 2 surge arrester for TT and TN systems in only two DIN modules, aimed at boards where a full four-module device will not fit.
- Compact three-phase Type 2 protection
- TT and TN systems
- In 5kA L-N / 20kA N-PE, UP 1.5kV
- Only two DIN modules
- Green/red status indication
12 in stock
UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 2-3 working days.
Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.
Project quantities or a lead time to check? Request a quote
Specifications
Electrical
| Supply | Three phase |
|---|---|
| Earthing system | TT, TN-S, TN-C-S (PME) |
| Earthing system (as supplied) | TT/TN |
| Remote signalling contact | No |
| Application | Mains AC |
Protection
| SPD type | Type 2 |
|---|---|
| Nominal discharge current (In) | 5 kA |
| Voltage protection level (Up) | 1.5 kV |
Dimensions
| DIN rail width | 2 modules |
|---|
Fit
| Mounting | DIN rail |
|---|
Identification
| Brand | DEHN |
|---|---|
| Part number | 900455 |
| EAN | 5056551244375 |
| Range | DEHNguard compact |
More technical data
| Manufacturer | DEHN (DEHNguard 5kA, type DG TT 5 275) |
|---|---|
| SPD class | Type 2 to EN 61643-11 |
| Power supply system | three-phase TT / TN |
| Nominal a.c. voltage (UN) | 230/400V; UC 275V (L-N), 255V (N-PE) |
| Nominal discharge current In (8/20) | 5kA (L-N), 20kA (N-PE) |
| Max discharge current Imax (8/20) | 15kA (L-N), 40kA (N-PE) |
| Voltage protection level UP | 1.5kV; short-circuit withstand ISCCR 6kA |
| Max mains-side overcurrent protection | MCB C 63A; width 2 modules, IP20 |
| EAN as supplied | 5056551244375 |
Product details
Retrofitting surge protection to an existing three-phase board usually runs into the same problem: there are not four spare ways. The DG TT 5 275 puts three-phase TT and TN protection into two modules, trading maximum discharge capacity for a footprint that actually fits.
Key features
- Three-phase TT and TN protection in a two-module compact body
- Designed for retrofit and for small boards where space is the limiting factor
- N-PE path rated In 20kA and Imax 40kA with 100A follow current extinguishing
- Green/red operating state indication for a quick visual check
- Protected by an MCB C 63A rather than a large gG backup fuse
Typical applications
Best suited to small commercial and light industrial three-phase boards, retrofit work in occupied buildings, landlord and riser panels, shop and office fit-outs, and packaged plant such as air handling units or lift controllers where the control panel has limited spare ways. Where the board is at the origin of a building with a lightning protection system, a Type 1 device is still required upstream.
Compliance
Tested as a Type 2 device to EN 61643-11, with a UL 94 V-0 thermoplastic enclosure and IP20 protection for mounting inside an enclosure. BS 7671 requires transient overvoltage risk to be assessed and protection provided where the consequences justify it - note the lower L-N discharge ratings when assessing suitability against a full-size Type 2 device.
Order today for fast UK dispatch, or talk to us if you are unsure whether the compact or full-size arrester suits your board.