Trade only · Free delivery over £100 ex VAT
Product image 1

Mersen Surge-Trap SP12-50K-N Type 1+2 Replacement Cartridge, Neutral for 4 Pole TT Devices

Brand:
Mersen
Part number:
83120006
EAN:
8435297850359

Neutral-to-earth replacement cartridge for four-pole Mersen Surge-Trap STPT12 arresters on TT systems, rated Iimp 50kA with a 1.5kV protection level.

  • Neutral (N-PE) replacement cartridge
  • Iimp 50kA, Imax 50kA, Up 1.5kV
  • For 4 pole Surge-Trap TT devices
  • Mechanically coded, plug-in fit
£135.79 ex VAT£162.95 inc VAT

Out of stock

Datasheet (PDF)Opens in a new tab

UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 2-3 working days.

Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.

Project quantities or a lead time to check? Request a quote

Specifications

Electrical

Earthing system (as supplied)TT
ApplicationMains AC

Protection

SPD typeType 1+2

Fit

ReplacesN (N-PE)

Identification

BrandMersen
Part number83120006
EAN8435297850359
RangeMersen Surge-Trap STPT12
Part typeReplacement module / cartridge

More technical data

ManufacturerMersen (Surge-Trap, catalogue SP12-50K-N)
Functionneutral-to-earth (N-PE) replacement cartridge
For use infour-pole Surge-Trap STPT12 TT devices
Max continuous operating voltage Uc255V
Lightning impulse current Iimp (10/350)50kA; Imax (8/20): 50kA
Nominal discharge current In (8/20)50kA; Up at In: 1.5kV

Product details

A three-phase TT arrester sums the lightning current from all three lines into its neutral-to-earth path, which is why that cartridge is rated at 50kA rather than 25kA. This Mersen SP12-50K-N is the replacement for four-pole Surge-Trap STPT12 devices in that position.

Key features

  • Neutral-to-earth cartridge for four-pole Surge-Trap STPT12 TT arresters
  • Iimp of 50kA (10/350) and Imax of 50kA at a 1.5kV protection level
  • Rated for the summed discharge current of a three-phase TT installation
  • Mechanically coded and plug-in, so replacement needs no re-termination
  • Not interchangeable with the 25kA cartridge used in two-pole devices

Typical applications

Four-pole TT arresters protect three-phase electrode-earthed intakes on farms and agricultural estates, water and wastewater works, quarries and outdoor process plant, telecoms compounds and renewable energy installations. Keeping the neutral cartridge in stock is worthwhile because it is the pole that takes the heaviest duty.

Compliance

Part of the Surge-Trap STPT12 Type 1+2 / Class I+II range tested to IEC 61643-11 and EN 61643-11. Cartridges are mechanically coded to their position - fit only the cartridge specified for the pole and device being serviced.

Order today for fast UK dispatch, or send us the arrester catalogue number and we will confirm the right cartridge.