Trade only · Free delivery over £100 ex VAT
Product image 1

Europa Sentinel SLCU6EV40B-SPD EV Charger Board, 100A Switch, 40A MCB, Type B RCCB, SPD

Brand:
Europa Components
Part number:
SLCU6EV40B-SPD
EAN:
5056551233720

The fullest specification in Europa's Sentinel EV board range: a six-module metal-clad board with 100A main switch, 40A MCB, Type B RCCB and Type 2 SPD.

  • Type B RCCB and Type 2 SPD in one board
  • 100A main switch and 40A MCB fitted
  • Fullest specification in the Sentinel EV range
  • Six-module metal-clad, supplied populated
  • IP20, IK05, indoor installation
£149.99 ex VAT£179.99 inc VAT

Out of stock

Datasheet (PDF)Opens in a new tab

UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 2-3 working days.

Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.

Project quantities or a lead time to check? Request a quote

Specifications

Electrical

Rated current40 A

Protection

RCD typeType B
IP ratingIP20
Surge protection fittedYes (Type 2)

Dimensions

DIN rail width6 modules

Identification

BrandEuropa Components
Part numberSLCU6EV40B-SPD
EAN5056551233720

More technical data

ManufacturerEuropa Components, Sentinel EV range
Configuration6 module, 100A switch, 40A MCB, RCCB Type B, Type 2 SPD
Enclosuremetal-clad, single phase
Rated voltage230V AC, 50Hz
Degree of protectionIP20 (indoor installation only)
Mechanical impact protectionIK05
Max cable capacity35mm² main switch and RCCB, 16mm² MCB

Product details

The Europa Sentinel SLCU6EV40B-SPD is the fullest specification in this group of EV charger supply boards, combining a 100A main switch, a 40A MCB, a Type B RCCB and a Type 2 surge protection device in one six-module metal-clad assembly. It is the board to specify when the charger does not provide its own DC fault protection and the installation also warrants surge protection, which covers a large share of external charge points on long supply runs.

Key features

  • Type B RCCB, detecting smooth DC residual current as well as AC and pulsating DC
  • Type 2 surge protection device factory-fitted and wired
  • 100A main switch and 40A outgoing MCB
  • Six-module metal-clad enclosure, delivered populated so site work is termination rather than assembly
  • Labelled earth and neutral bars at the top and a DIN rail position that leaves room to dress conductors
  • Knockouts on the top, bottom and both sides for flexible cable entry

Typical applications

Driveway, car park and workplace charge points fed by a long external run, installations where a BS 7671 risk assessment calls for surge protection, and estates standardising on one fully-specified board rather than checking DC fault protection charger by charger.

Compliance

Built to BS EN 61439-3, with the fitted devices declared to BS EN 60947-3 (main switch), BS EN 61008-1 (RCCB) and BS EN 60898-1 (MCB). Europa states that the range is designed to meet the requirements of the 18th Edition of BS 7671. The board is rated IP20 and is for indoor installation only, so an outdoor charge point must be fed from a board sited inside the building.

In stock for fast UK dispatch at trade-direct prices.