800 A neutral link for a 3-pole 1250AF incomer in the TRPHXINC housing of a Resilience Plus 800 A panel board. Terasaki part number TRPHXNL.

  • For a 3-pole 1250AF incomer, 800 A
  • Fits the TRPHXINC incomer housing
  • Resilience Plus 800 A boards
  • Not needed with a 4-pole incomer
£328.58 ex VAT£394.30 inc VAT

Available to order

Datasheet (PDF)Opens in a new tabBuild a board with this partConfigure a complete Terasaki Resilience panel board online: incomer, outgoing MCCBs, surge and metering, with a drawing and parts list.

UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 3-5 working days.

Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.

Project quantities or a lead time to check? Request a quote

Specifications

Electrical

Rated current800 A

Fit

Panelboard rangeResilience Plus
What does this mean?

Modular: a separate incomer housing beside the panel board, with add-on enclosures and cableways. 400 A or 800 A busbars, 6 to 18 outgoing ways, outgoing MCCBs up to 250 A (400 A on the twin board), Form 3a or 3b Type 2, doors optional.

Identification

BrandTerasaki
Part numberTRPHXNL
RangeTerasaki Resilience
TypeNeutral link

More technical data

Part typeneutral link for a 3-pole incomer
Frame1250AF; rating 800 A
HousingTRPHXINC (Resilience Plus 800 A boards)
Board busbarscertified, 50 kA for 1 s

Product details

The Terasaki TRPHXNL is the 800 A neutral link for a 1250AF 3-pole incoming device in the Resilience Plus TRPHXINC housing, the incomer arrangement that gives an 800 A board its full rating. With a 3-pole device the board needs this link for its neutral connection; a 4-pole device does not.

Key features

  • For a 3-pole 1250AF incomer in the TRPHXINC housing
  • Rated 800 A
  • Suits the 3-pole S1250-NN switch-disconnector and S1250-SE electronic MCCB
  • Not needed with a 4-pole incomer

Typical applications

800 A Resilience Plus boards on a main supply, fed through the TRPHXINC housing with a 3-pole S1250 device rated 800 A. Order the link with the housing and the device so the incomer is complete, and remember that the board only reaches its full 800 A through this 1250AF arrangement.

Compliance

Compliance belongs to the assembled board: Terasaki states that Resilience Plus 800 A panel boards meet the requirements of BS EN 61439-2, with certified busbars rated 50 kA for 1 s.

What it fits: The TRPHXINC housing on Resilience Plus 800 A boards, the twin board included, with a 3-pole device: the S1250-NN switch-disconnector 106125 or the S1250-SE electronic MCCB 553240, both 800 A. Boards fed through TRPDHINC use the TRPDHNL link.