Illustration - our own representative render, not a photograph; see the datasheet for exact details.
Terasaki S250-SJ 50A 3-Pole MCCB, TemBreak 2 Lite 250A Frame, 40kA (933561)
- Brand:
- Terasaki
- Part number:
- 933561
Three-pole, 50 A TemBreak 2 Lite S250-SJ moulded-case circuit breaker with adjustable thermal-magnetic protection and 40 kA Icu (20 kA Ics) at 400/415 V AC. Terasaki part number 933561.
- 50 A, 3-pole, TemBreak 2 Lite 250 A frame
- Icu 40 kA, Ics 20 kA at 400/415 V AC
- Adjustable thermal and magnetic trips
- TemBreak 2 Lite accessory range
- Outgoing device for Resilience Plus boards
Available to order
UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 3-5 working days.
Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.
Project quantities or a lead time to check? Request a quote
Specifications
Electrical
| Rated current | 50 A |
|---|---|
| Poles / neutral | 3 pole |
| Frame size | 250 A |
Protection
| Trip unit | Thermal-magnetic |
|---|---|
| Breaking capacity (Icu) | 40 kA |
Fit
| Panelboard range | Resilience PlusWhat does this mean?Modular: a separate incomer housing beside the panel board, with add-on enclosures and cableways. 400 A or 800 A busbars, 6 to 18 outgoing ways, outgoing MCCBs up to 250 A (400 A on the twin board), Form 3a or 3b Type 2, doors optional. |
|---|
Identification
| Brand | Terasaki |
|---|---|
| Part number | 933561 |
| Range | Terasaki TemBreak2 Lite |
More technical data
| Series | TemBreak 2 Lite S250-SJ, 250 A frame, 3 poles |
|---|---|
| Rated current In | 50 A at 50 °C |
| Trip unit | adjustable thermal-magnetic |
| Icu / Ics at 400/415 V AC | 40 kA / 20 kA |
| Icu at 440 V AC | 30 kA; at 250 V DC: 25 kA |
| Ue | 690 V AC (50/60 Hz) and 250 V DC; Ui: 800 V; Uimp: 8 kV |
| Utilisation category | A |
| Connection | front, M8 terminal screws (lug or bar up to 25 mm wide, 7 mm thick) |
| Dimensions (W x H x D) | 105 x 165 x 68 mm; weight 1.5 kg |
| Endurance at 415 V AC | 6,000 electrical and 18,000 mechanical cycles |
Product details
Terasaki S250-SJ 933561 is a 50 A, 3-pole TemBreak 2 Lite moulded-case circuit breaker on the 250 A frame, with adjustable thermal-magnetic protection and 40 kA Icu at 400/415 V AC. Terasaki lists it as an outgoing device for Resilience Plus 6, 12 and 18 way boards.
Key features
- TemBreak 2 Lite device with adjustable thermal and magnetic trips
- Icu 40 kA, Ics 20 kA at 400/415 V AC
- Suits AC systems to 690 V and DC to 250 V
Typical applications
A 50 A three-phase way for small sub-distribution boards and plant. Note the service rating: Ics is 20 kA at 400/415 V, half the Icu. If the design needs more, the TemBreak 2 S160-NJ 50 A (326851) is rated 36 kA Icu and Ics, and the S160-GJ 50 A (327025) 65 kA Icu. Our Panel Builder adds it to a Resilience Plus layout and parts list.
Compliance
Electrical characteristics to IEC 60947-2 and EN 60947-2 (Terasaki datasheet).
Lite accessories that fit: auxiliary switch 002489, alarm switch 002557, a shunt trip or an under-voltage release (one trip-coil pocket, so not both), handle lock 064906, terminal covers 065309, 065316 and 080456, terminal cover lock 065644, cable clamps 062247 and 062254, and interpole barrier 065729. Interpole barriers and standard terminal covers cannot be fitted together.
Genuine Terasaki product. Add it to your cart, or ask us about project quantities.