Trade only · Free delivery over £100 ex VAT
Product image 1

Illustration - our own representative render, not a photograph; see the datasheet for exact details.

Terasaki S160-GJ 63A 3-Pole MCCB, TemBreak 2 160A Frame, 65kA (327032)

Brand:
Terasaki
Part number:
327032

Three-pole, 63 A TemBreak 2 S160-GJ moulded-case circuit breaker with adjustable thermal-magnetic protection and 65 kA Icu (36 kA Ics) at 400/415 V AC. Terasaki part number 327032.

  • 63 A, 3-pole, TemBreak 2 160 A frame
  • Icu 65 kA, Ics 36 kA at 400/415 V AC
  • Adjustable thermal and magnetic trips
  • Front connection, M8 terminals
  • Outgoing device for Resilience Plus boards
£304.80 ex VAT£365.76 inc VAT

Available to order

Datasheet (PDF)Opens in a new tabBuild a board with this partConfigure a complete Terasaki Resilience panel board online: incomer, outgoing MCCBs, surge and metering, with a drawing and parts list.

UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 3-5 working days.

Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.

Project quantities or a lead time to check? Request a quote

Specifications

Electrical

Rated current63 A
Poles / neutral3 pole
Frame size160 A

Protection

Trip unitThermal-magnetic
Breaking capacity (Icu)65 kA

Fit

Panelboard rangeResilience Plus
What does this mean?

Modular: a separate incomer housing beside the panel board, with add-on enclosures and cableways. 400 A or 800 A busbars, 6 to 18 outgoing ways, outgoing MCCBs up to 250 A (400 A on the twin board), Form 3a or 3b Type 2, doors optional.

Identification

BrandTerasaki
Part number327032
RangeTerasaki TemBreak2

More technical data

SeriesTemBreak 2 S160-GJ, 160 A frame, 3 poles
Rated current In63 A at 50 °C
Trip unitadjustable thermal-magnetic
Icu / Ics at 400/415 V AC65 kA / 36 kA
Icu at 440 V AC50 kA; at 250 V DC: 40 kA
Ue690 V AC (50/60 Hz) and 250 V DC; Ui: 800 V; Uimp: 8 kV
Utilisation categoryA
Connectionfront, M8 terminal screws (lug or bar up to 25 mm wide, 7 mm thick)
Dimensions (W x H x D)105 x 165 x 68 mm; weight 1.5 kg
Endurance at 415 V AC20,000 electrical and 30,000 mechanical cycles

Product details

Terasaki S160-GJ 327032 is a 63 A, 3-pole TemBreak 2 moulded-case circuit breaker rated 65 kA Icu at 400/415 V AC, with adjustable thermal and magnetic trips on the 160 A frame. It is one of Terasaki's outgoing devices for Resilience Plus 6, 12 and 18 way boards.

Key features

  • Higher-breaking version of the S160-NJ: 65 kA Icu at 400/415 V AC against 36 kA
  • Ics 36 kA at 400/415 V AC, the same as the NJ
  • Thermal and magnetic trips, both adjustable
  • Suits AC systems to 690 V and DC to 250 V

Typical applications

A 63 A three-phase way for sub-mains and plant where fault levels run higher than 36 kA. Below that, the S160-NJ 63 A (326868) does the same job at 36 kA; the GJ's Ics stays at 36 kA, so the step up is in ultimate breaking capacity. The Panel Builder on this site draws the board and lists the parts.

Compliance

Electrical characteristics to IEC 60947-2 and EN 60947-2 (Terasaki datasheet).

Accessories that fit: auxiliary switch 000348, alarm switch 000744, a shunt trip or an under-voltage release (one trip-coil pocket, so not both), and toggle lock 037016.

Genuine Terasaki product. Add it to your cart, or contact us about a board schedule.