Illustration - our own representative render, not a photograph; see the datasheet for exact details.
Terasaki S160-GJ 160A 3-Pole MCCB, TemBreak 2 160A Frame, 65kA (327063)
- Brand:
- Terasaki
- Part number:
- 327063
Three-pole, 160 A TemBreak 2 S160-GJ moulded-case circuit breaker with adjustable thermal-magnetic protection and 65 kA Icu (36 kA Ics) at 400/415 V AC. Terasaki part number 327063.
- 160 A, 3-pole, TemBreak 2 160 A frame
- Icu 65 kA, Ics 36 kA at 400/415 V AC
- Adjustable thermal and magnetic trips
- Front connection, M8 terminals
- Outgoing device for Resilience Plus boards
Available to order
UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 3-5 working days.
Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.
Project quantities or a lead time to check? Request a quote
Specifications
Electrical
| Rated current | 160 A |
|---|---|
| Poles / neutral | 3 pole |
| Frame size | 160 A |
Protection
| Trip unit | Thermal-magnetic |
|---|---|
| Breaking capacity (Icu) | 65 kA |
Fit
| Panelboard range | Resilience PlusWhat does this mean?Modular: a separate incomer housing beside the panel board, with add-on enclosures and cableways. 400 A or 800 A busbars, 6 to 18 outgoing ways, outgoing MCCBs up to 250 A (400 A on the twin board), Form 3a or 3b Type 2, doors optional. |
|---|
Identification
| Brand | Terasaki |
|---|---|
| Part number | 327063 |
| Range | Terasaki TemBreak2 |
More technical data
| Series | TemBreak 2 S160-GJ, 160 A frame, 3 poles |
|---|---|
| Rated current In | 160 A at 50 °C |
| Trip unit | adjustable thermal-magnetic |
| Icu / Ics at 400/415 V AC | 65 kA / 36 kA |
| Icu at 440 V AC | 50 kA; at 250 V DC: 40 kA |
| Ue | 690 V AC (50/60 Hz) and 250 V DC; Ui: 800 V; Uimp: 8 kV |
| Utilisation category | A |
| Connection | front, M8 terminal screws (lug or bar up to 25 mm wide, 7 mm thick) |
| Dimensions (W x H x D) | 105 x 165 x 68 mm; weight 1.5 kg |
| Endurance at 415 V AC | 20,000 electrical and 30,000 mechanical cycles |
Product details
Terasaki S160-GJ 327063 is a 160 A, 3-pole TemBreak 2 moulded-case circuit breaker at the full rating of the 160 A frame, with 65 kA Icu at 400/415 V AC and adjustable thermal-magnetic protection. It is one of Terasaki's outgoing devices for Resilience Plus 6, 12 and 18 way boards.
Key features
- Higher-breaking version of the S160-NJ: 65 kA Icu at 400/415 V AC against 36 kA
- Ics 36 kA at 400/415 V AC, the same as the NJ
- Thermal and magnetic trips, both adjustable
- Suits AC systems to 690 V and DC to 250 V
Typical applications
Large sub-mains and plant rooms of up to 160 A where the prospective fault current exceeds 36 kA. The S160-NJ 160 A (326899) covers lower fault levels, and the S250-GE 160 A (337925) adds electronic protection at 65 kA. Plan the whole board in our Panel Builder, with a drawing and parts list.
Compliance
Electrical characteristics to IEC 60947-2 and EN 60947-2 (Terasaki datasheet).
Accessories that fit: auxiliary switch 000348, alarm switch 000744, a shunt trip or an under-voltage release (one trip-coil pocket, so not both), and toggle lock 037016.
Genuine Terasaki product. Add it to your cart, or contact us about a board schedule.