Trade only · Free delivery over £100 ex VAT
Product image 1

Terasaki's catalogue picture of this product family; see the datasheet for exact details.

Terasaki 065453 Rear Connection Terminal Cover 3-Pole, for TemBreak 2 Lite 160A Frame

Brand:
Terasaki
Part number:
065453

Single terminal cover for rear-connected 3-pole TemBreak 2 Lite breakers on the 160 A frame, closing off the terminals from the front and top. Terasaki part number 065453.

  • Rear-connection terminal cover (CR)
  • 3-pole, TemBreak 2 Lite 160A frame
  • 4 mm Megger test hole per terminal
  • One cover per breaker end
£19.39 ex VAT£23.27 inc VAT

Available to order

Datasheet (PDF)Opens in a new tabBuild a board with this partConfigure a complete Terasaki Resilience panel board online: incomer, outgoing MCCBs, surge and metering, with a drawing and parts list.

UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 3-5 working days.

Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.

Project quantities or a lead time to check? Request a quote

Specifications

Electrical

Poles / neutral3 pole

Fit

Fits deviceTerasaki S160-SCJ
Fits MCCB frame160 A
Panelboard rangeResilience Standard, Resilience Plus
What does this mean?

Incomer and outgoing ways in one wall-mounted board. 250 A or 400 A busbars, 4 to 18 outgoing ways, outgoing MCCBs up to 125 A, Form 3b Type 2, doors included. Modular: a separate incomer housing beside the panel board, with add-on enclosures and cableways. 400 A or 800 A busbars, 6 to 18 outgoing ways, outgoing MCCBs up to 250 A (400 A on the twin board), Form 3a or 3b Type 2, doors optional.

Identification

BrandTerasaki
Part number065453
RangeTerasaki TemBreak2 Lite
TypeTerminal cover

More technical data

Typeterminal cover for rear connection
FrameTemBreak 2 Lite 160 A
Width75 mm
Test access4 mm hole per terminal
Colourgrey
Suppliedone cover, for one end of the breaker

Product details

The Terasaki 065453 is a terminal cover for 3-pole TemBreak 2 Lite breakers on the 160 A frame that are connected from the rear. With the conductors taken off the back of the breaker, the cover closes the terminal openings so they cannot be reached from the front or from above. Each cover protects one end of the breaker.

Key features

  • Rear-connection type (Terasaki CR), not a front-connection cover
  • Shields the terminal area at the front and on top
  • A 4 mm hole at each terminal allows insulation-resistance (Megger) testing with the cover in place
  • Grey; 75 mm wide for the 3-pole body
  • Line and load ends are covered separately, so a breaker needs two for full coverage

Typical applications

Rear-connected 160 A frame breakers in switchboards and panels where bars or cables are brought to the back of the device, and replacement of rear covers lost or damaged during alterations. Interpole barriers cannot be fitted together with a terminal cover.

Fits the 3-pole S160-SCJ when it is rear-connected. A front-connected S160-SCJ takes Terasaki's front-connection cover, part number 065248, instead.

Add it to your cart, two per breaker where both ends need covering.