Trade only · Free delivery over £100 ex VAT
Product image 1

Illustration - our own representative render, not a photograph; see the datasheet for exact details.

Terasaki TRPDHINC 400A/630A Incomer Housing for 800AF Device, for Resilience Plus Panelboards

Brand:
Terasaki
Part number:
TRPDHINC

Incomer housing for an 800AF TemBreak 2 MCCB or switch-disconnector, serving Resilience Plus 400 A boards (400 A) and 800 A boards (630 A), 762 mm high. Terasaki part number TRPDHINC.

  • For 800AF TemBreak 2 incomers
  • 400 A on 400 A boards, 630 A on 800 A boards
  • 762 mm (5 modules), 750 mm wide, 45 kg
  • Takes incoming meter and surge kits
  • Top-entry option with a TRPEK
£877.25 ex VAT£1,052.70 inc VAT

Quoted per job

Datasheet (PDF)Opens in a new tabBuild a board with this partConfigure a complete Terasaki Resilience panel board online: incomer, outgoing MCCBs, surge and metering, with a drawing and parts list.

Delivered on a pallet from our workshop, delivery quoted with your price; parts usually 3-5 working days, a board built and tested by us 8-12 working days.

Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.

Project quantities or a lead time to check? Request a quote

Specifications

Electrical

Rated current630 A
Frame size800 A

Dimensions

Weight45 kg
Height in modules5 modules

Fit

Panelboard rangeResilience Plus
What does this mean?

Modular: a separate incomer housing beside the panel board, with add-on enclosures and cableways. 400 A or 800 A busbars, 6 to 18 outgoing ways, outgoing MCCBs up to 250 A (400 A on the twin board), Form 3a or 3b Type 2, doors optional.

Identification

BrandTerasaki
Part numberTRPDHINC
RangeTerasaki Resilience
TypeIncomer housing

More technical data

Incoming device frame800AF
Maximum rating400 A on a 400 A board; 630 A on an 800 A board
FixingM8 at 650 mm horizontal and 609.6 mm vertical centres
Largest incoming cable on the S800 device2 x 240 mm² (standard lug), 2 x 300 mm² (reduced palm lug)
Neutral link for a 3-pole deviceTRPDHNL
Meter kitsTRPDHMKE, TRPDHMKME (MID); surge kits: TRPDHSK1E (Type 1), TRPDHSK2E (Type 2)
  • Height 762 mm (5 modules); width 750 mm; depth 200 mm

Product details

The Terasaki TRPDHINC is the 5-module incomer housing for an 800AF TemBreak 2 device, and the only Resilience Plus incomer housing listed for both the 400 A and the 800 A boards. On a 400 A board it carries an incomer rated up to 400 A; on an 800 A board it takes a 630 A device, which limits that board to 630 A.

Key features

  • Takes an 800AF MCCB or switch-disconnector, 3- or 4-pole
  • Holds Terasaki's incoming meter mounting and surge kits
  • 762 mm high (5 modules), 750 mm wide, 200 mm deep, 45 kg
  • Can be inverted and fitted above the board for a top-entry supply, with one TRPEK

Typical applications

A 400 A board that needs a 400 A incomer, or an 800 A board where 630 A is enough. For the full 800 A, choose the TRPHXINC housing with a 1250AF device instead.

Compliance

Compliance belongs to the assembled board: Terasaki states that Resilience Plus panel boards meet the requirements of BS EN 61439-2, with certified busbars rated 36 kA (400 A boards) or 50 kA (800 A boards) for 1 s.

What it fits: All Resilience Plus boards, 400 A and 800 A, including the twin 400AF board. On a 400 A board: S800-NN switch-disconnector 106101 (3P) or 106118 (4P), S800-NF MCCB 497995 (3P) or 498008 (4P). On an 800 A board: S800-NJ MCCB 812149 (3P) or 812163 (4P), S800-NE electronic MCCB 812262 (3P) or 812309 (4P). Incomer housings have no door kit.

Configure your board in the Panel Builder or ask us for a quote.