Terasaki S250-SN 250A 4-Pole MCCB Switch-Disconnector, TemBreak 2 Lite 250A Frame (930973)
- Brand:
- Terasaki
- Part number:
- 930973
Non-automatic 250 A 4-pole switch-disconnector on the TemBreak 2 Lite 250 A frame for switching and isolating the supply to a Resilience Standard panel board; it has no overcurrent release. Terasaki part number 930973.
- 250 A, 4-pole switch-disconnector, TemBreak 2 Lite 250 A frame
- No overcurrent release: needs upstream protection
- AC-23A at up to 690 V AC, Icw 3 kA for 0.3 s
- Front connection, M8 terminal screws
- Incomer for Resilience Standard boards
Available to order
UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 3-5 working days.
Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.
Project quantities or a lead time to check? Request a quote
Specifications
Electrical
| Rated current | 250 A |
|---|---|
| Poles / neutral | 4 pole |
| Frame size | 250 A |
Fit
| Panelboard range | Resilience StandardWhat does this mean?Incomer and outgoing ways in one wall-mounted board. 250 A or 400 A busbars, 4 to 18 outgoing ways, outgoing MCCBs up to 125 A, Form 3b Type 2, doors included. |
|---|
Identification
| Brand | Terasaki |
|---|---|
| Part number | 930973 |
| Range | Terasaki TemBreak2 Lite |
More technical data
| Series | TemBreak 2 Lite S250-SN, 250 A frame, 4-pole, non-automatic |
|---|---|
| Rated current Ie | 250 A |
| Ue | 690 V AC 50/60 Hz, 250 V DC; Ui 800 V; Uimp 8 kV |
| Utilisation category | AC-23A, DC-22A |
| Dimensions (W x H x D) | 140 x 165 x 68 mm; weight 1.9 kg |
| Endurance | 6,000 electrical (415 V AC), 18,000 mechanical operations |
- Icm 6 kA peak; Icw 3 kA (0.3 s)
Product details
The Terasaki S250-SN 930973 is a 250 A, 4-pole moulded-case switch-disconnector on the TemBreak 2 Lite 250 A frame. It switches load current (AC-23A) and isolates the circuit, but it has no thermal or magnetic release, so it gives no overload or short-circuit protection: the supply must be protected upstream.
Key features
- Ue up to 690 V AC or 250 V DC; Icw 3 kA for 0.3 s, Icm 6 kA peak
- Front connection with M8 terminal screws; extension bars, cable clamps and rear connection optional
- Direct opening action and toggle operation; door- or breaker-mounted handles and motor operation optional
Typical applications
Main switch of a Resilience Standard MCCB panel board fed from a protected circuit, such as a fused way in the upstream switchboard. Its fourth pole switches and isolates the neutral with the phases. It also serves as an on-load isolator for sub-mains. In the Panel Builder it can be chosen as the incomer of a complete board.
Compliance
Rated to IEC 60947-3 and EN 60947-3 (also AS/NZS 3947-3), as stated on the series datasheet.
Accessories that fit: auxiliary switch 002489; alarm switch 002557; shunt trips 003417, 003424, 003431, 003448, 003455, 003462 and 003479, or under-voltage releases 003547, 003554, 003561, 003578, 003585 and 003592 (one trip-coil pocket: one or the other, not both); handle lock 064906; terminal covers 065309, 065316 and 080456 with cover lock 065644; cable clamps 062247 and 062254; interpole barrier 065729. Interpole barriers and standard terminal covers cannot be fitted together.
Genuine Terasaki product. Add it to your cart, or ask us about project quantities.