Terasaki E160-SF 16A 1-Pole MCCB, TemBreak 2 Lite 160A Frame, 25kA (591761)

Brand:
Terasaki
Part number:
591761

16 A single-pole TemBreak 2 Lite MCCB (fixed thermal-magnetic, 25 kA at 220/240 V AC) for lighting and control circuits on a Resilience Standard panelboard. Terasaki part number 591761.

  • 16 A single pole, TemBreak 2 Lite 160 A frame
  • Icu 25 kA, Ics 13 kA at 220/240 V AC
  • Fixed thermal-magnetic, magnetic trip 600 A
  • Factory-fitted cable clamps (FW), 25 mm wide
  • Outgoing device for Resilience Standard boards
£127.84 ex VAT£153.41 inc VAT

Available to order

Datasheet (PDF)Opens in a new tabBuild a board with this partConfigure a complete Terasaki Resilience panel board online: incomer, outgoing MCCBs, surge and metering, with a drawing and parts list.

UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 3-5 working days.

Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.

Project quantities or a lead time to check? Request a quote

Specifications

Electrical

Rated current16 A
Poles / neutral1 pole
Frame size160 A

Protection

Trip unitThermal-magnetic

Fit

Panelboard rangeResilience Standard
What does this mean?

Incomer and outgoing ways in one wall-mounted board. 250 A or 400 A busbars, 4 to 18 outgoing ways, outgoing MCCBs up to 125 A, Form 3b Type 2, doors included.

Identification

BrandTerasaki
Part number591761
RangeTerasaki TemBreak2 Lite

More technical data

SeriesTemBreak 2 Lite E160-SF, 1 pole, 160 A frame
Rated current In16 A at 50 °C
Breaking capacity at 220/240 V ACIcu 25 kA, Ics 13 kA
Trip unitfixed thermal, fixed magnetic; magnetic trip 600 A ±120 A (AC)
Utilisation categoryA
Connectionfront, with factory-fitted cable clamp (FW)
Dimensions (W x H x D)25 x 130 x 68 mm; weight 0.3 kg
  • Ue 240 V AC (50/60 Hz); Ui 690 V; Uimp 8 kV

Product details

A 16 A single-pole moulded-case circuit breaker from Terasaki's TemBreak 2 Lite E160-SF range, rated 25 kA (Icu) at 220/240 V AC. It is the lowest rating in the single-pole series and one of the outgoing devices Terasaki lists for Resilience Standard panelboards.

Key features

  • 16 A single pole on the 160 A TemBreak 2 Lite frame, 25 mm wide
  • Fixed thermal and fixed magnetic trips, so there is nothing to set on site
  • Cable clamp terminals (FW) fitted at the factory
  • Takes auxiliary and alarm switches, a shunt trip or under-voltage release, and a handle lock

Typical applications

Use it for light single-phase loads taken straight from the board: a lighting circuit, a control or alarm panel supply, a door entry or BMS controller, or a small extract fan. The fixed magnetic trip of 600 A is a high multiple of 16 A, so compare it with the earth fault loop impedance when you prove disconnection times. Our online Panel Builder can place it on an outgoing way of a Resilience Standard board and produce the drawing and parts list.