Illustration - our own representative render, not a photograph; see the datasheet for exact details.
Terasaki E160-SF 16A 1-Pole MCCB, TemBreak 2 Lite 160A Frame, 25kA (591761)
- Brand:
- Terasaki
- Part number:
- 591761
16 A single-pole TemBreak 2 Lite MCCB (fixed thermal-magnetic, 25 kA at 220/240 V AC) for lighting and control circuits on a Resilience Standard panelboard. Terasaki part number 591761.
- 16 A single pole, TemBreak 2 Lite 160 A frame
- Icu 25 kA, Ics 13 kA at 220/240 V AC
- Fixed thermal-magnetic, magnetic trip 600 A
- Factory-fitted cable clamps (FW), 25 mm wide
- Outgoing device for Resilience Standard boards
Available to order
UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 3-5 working days.
Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.
Project quantities or a lead time to check? Request a quote
Specifications
Electrical
| Rated current | 16 A |
|---|---|
| Poles / neutral | 1 pole |
| Frame size | 160 A |
Protection
| Trip unit | Thermal-magnetic |
|---|
Fit
| Panelboard range | Resilience StandardWhat does this mean?Incomer and outgoing ways in one wall-mounted board. 250 A or 400 A busbars, 4 to 18 outgoing ways, outgoing MCCBs up to 125 A, Form 3b Type 2, doors included. |
|---|
Identification
| Brand | Terasaki |
|---|---|
| Part number | 591761 |
| Range | Terasaki TemBreak2 Lite |
More technical data
| Series | TemBreak 2 Lite E160-SF, 1 pole, 160 A frame |
|---|---|
| Rated current In | 16 A at 50 °C |
| Breaking capacity at 220/240 V AC | Icu 25 kA, Ics 13 kA |
| Trip unit | fixed thermal, fixed magnetic; magnetic trip 600 A ±120 A (AC) |
| Utilisation category | A |
| Connection | front, with factory-fitted cable clamp (FW) |
| Dimensions (W x H x D) | 25 x 130 x 68 mm; weight 0.3 kg |
- Ue 240 V AC (50/60 Hz); Ui 690 V; Uimp 8 kV
Product details
A 16 A single-pole moulded-case circuit breaker from Terasaki's TemBreak 2 Lite E160-SF range, rated 25 kA (Icu) at 220/240 V AC. It is the lowest rating in the single-pole series and one of the outgoing devices Terasaki lists for Resilience Standard panelboards.
Key features
- 16 A single pole on the 160 A TemBreak 2 Lite frame, 25 mm wide
- Fixed thermal and fixed magnetic trips, so there is nothing to set on site
- Cable clamp terminals (FW) fitted at the factory
- Takes auxiliary and alarm switches, a shunt trip or under-voltage release, and a handle lock
Typical applications
Use it for light single-phase loads taken straight from the board: a lighting circuit, a control or alarm panel supply, a door entry or BMS controller, or a small extract fan. The fixed magnetic trip of 600 A is a high multiple of 16 A, so compare it with the earth fault loop impedance when you prove disconnection times. Our online Panel Builder can place it on an outgoing way of a Resilience Standard board and produce the drawing and parts list.
Compliance
Terasaki declares the electrical characteristics to IEC 60947-2 and EN 60947-2, alongside JIS C 8201-2-1 Annex 1 and NEMA AB-1.
Listed accessories: auxiliary switch 002489, alarm switch 002557 and handle lock 064906, plus a shunt trip or an under-voltage release (one per breaker, several coil voltages).
Genuine Terasaki product. Add it to your cart, or ask us about project quantities.