
Illustration - our own representative render, not a photograph; see the datasheet for exact details.
Terasaki S250-GE 125A 3-Pole Electronic MCCB, TemBreak 2 250A Frame, 65kA (332104)
- Brand:
- Terasaki
- Part number:
- 332104
Three-pole, 125 A TemBreak 2 S250-GE electronic moulded-case circuit breaker with a current setting of 50 A to 125 A and 65 kA Icu (36 kA Ics) at 400/415 V AC. Terasaki part number 332104.
- 125 A, 3-pole, TemBreak 2 250 A frame
- Electronic trip, current setting 50-125 A
- Icu 65 kA, Ics 36 kA at 400/415 V AC
- Short-time pick-up and delay settings
- Outgoing device for Resilience Plus boards
Available to order
UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 3-5 working days.
Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.
Project quantities or a lead time to check? Request a quote
Specifications
Electrical
| Rated current | 125 A |
|---|---|
| Poles / neutral | 3 pole |
| Frame size | 250 A |
Protection
| Trip unit | Electronic |
|---|---|
| Breaking capacity (Icu) | 65 kA |
Fit
| Panelboard range | Resilience PlusWhat does this mean?Modular: a separate incomer housing beside the panel board, with add-on enclosures and cableways. 400 A or 800 A busbars, 6 to 18 outgoing ways, outgoing MCCBs up to 250 A (400 A on the twin board), Form 3a or 3b Type 2, doors optional. |
|---|
Identification
| Brand | Terasaki |
|---|---|
| Part number | 332104 |
| Range | Terasaki TemBreak2 |
More technical data
| Series | TemBreak 2 S250-GE, 250 A frame, 3 poles |
|---|---|
| Rated current In | 125 A at 50 °C; current setting 50-125 A |
| Trip unit | electronic (microprocessor) |
| Icu / Ics at 400/415 V AC | 65 kA / 36 kA |
| Ue | 690 V AC (50/60 Hz), AC only; Ui: 800 V; Uimp: 8 kV |
| Utilisation category | A |
| Connection | front, M8 terminal screws (lug or bar up to 25 mm wide, 7 mm thick) |
| Dimensions (W x H x D) | 105 x 165 x 103 mm; weight 2.3 kg |
| Endurance at 415 V AC | 30,000 cycles electrical and mechanical |
Product details
Terasaki S250-GE 332104 is a 125 A, 3-pole TemBreak 2 electronic moulded-case circuit breaker on the 250 A frame, rated 65 kA Icu and 36 kA Ics at 400/415 V AC, with a current setting from 50 A to 125 A. It is one of Terasaki's outgoing devices for Resilience Plus 6, 12 and 18 way boards.
Key features
- Electronic trip: current setting IR from 0.4 to 1.0 x In in seven steps
- Five selectable characteristics set the long-time delay, short-time pick-up (2.5, 5 or 10 x IR) and delay (0.1 or 0.2 s)
- Instantaneous trip at 14 x IR, capped at 13 x In
- Icu 65 kA, Ics 36 kA at 400/415 V AC
Typical applications
Sub-mains and plant feeders from 50 A to 125 A where the prospective fault current is above 36 kA and a settable pick-up helps discrimination. At 36 kA or below, the S250-NE 125 A (331800) is the equivalent; the S160-GJ 125 A (327056) is the 65 kA thermal-magnetic choice. Plan the whole board in our Panel Builder, with a drawing and parts list.
Compliance
Electrical characteristics to IEC 60947-2 and EN 60947-2 (Terasaki datasheet).
Accessories that fit: auxiliary switch 000348, alarm switch 000744, a shunt trip or an under-voltage release (one trip-coil pocket, so not both), terminal covers 080517 and 080654, cable clamps 081354 and 080586, and toggle lock 037016.
Genuine Terasaki product. Add it to your cart, or ask us about project quantities.

