Trade only · Free delivery over £100 ex VAT
Product image 1

DEHN DEHNguard DG M YPV SCI 1000 Type 2 Surge Protection Device, 3 Module 1000V DC PV

Brand:
DEHN
Part number:
952510
EAN:
4013364126428

Three-module Type 2 surge arrester for photovoltaic d.c. circuits up to 1000V, with DEHN's SCI disconnection and short-circuiting device to prevent d.c. switching arcs.

  • Type 2 PV protection to EN 50539-11
  • Up to 1000V d.c. array voltage
  • In 12.5kA, Imax 25kA, UP 4kV
  • SCI arc-free disconnection
  • Three DIN modules
£372.73 ex VAT£447.28 inc VAT

Out of stock

Datasheet (PDF)Opens in a new tab

UK delivery £9.95 ex VAT, free on orders of £100 ex VAT or more; usually 2-3 working days.

Minimum order £50 ex VAT. All prices exclude VAT, which is added at checkout.

Project quantities or a lead time to check? Request a quote

Specifications

Electrical

DC voltage1000 V DC
Earthing system (as supplied)Not applicable (DC)
Remote signalling contactNo
ApplicationSolar PV (DC)
ConnectionScrew terminals (DC +/-)

Protection

SPD typeType 2
Nominal discharge current (In)12.5 kA
Max discharge current (Imax)25 kA
Voltage protection level (Up)4 kV

Dimensions

DIN rail width3 modules

Fit

MountingDIN rail

Identification

BrandDEHN
Part number952510
EAN4013364126428
RangeDEHNguard YPV (PV)

More technical data

ManufacturerDEHN (DEHNguard modular YPV SCI, type DG M YPV SCI 1000)
SPD classType 2 to EN 50539-11 (photovoltaic)
Max PV voltage (UCPV)1000V d.c.; short-circuit current rating ISCPV 1000A
Nominal discharge current In (8/20)12.5kA per pole to PE
Max discharge current Imax (8/20)25kA; total discharge current 40kA
Voltage protection level UP4kV (3.5kV at 5kA); response time 25ns
Conductor range1.5 to 35mm2 stranded / 25mm2 flexible
  • Width 3 modules (DIN 43880), IP20, 35mm DIN rail to EN 60715, -40 to +80C

Product details

Direct current does not self-extinguish the way a.c. does, which is why a failed varistor on a PV string can start a fire rather than simply stop working. The DG M YPV SCI 1000 combines Type 2 protection for 1000V d.c. arrays with DEHN's patented SCI disconnection and short-circuiting device, so a module reaching end of life is isolated safely without drawing an arc.

Key features

  • Type 2 protection for photovoltaic d.c. circuits up to 1000V UCPV
  • SCI principle combines disconnection and short-circuiting to prevent d.c. switching arcs
  • Integrated d.c. fuses allow protection modules to be replaced without arc formation
  • Y-configuration protects both d.c. poles and the array against earth
  • Rated for a 1000A PV short-circuit current

Typical applications

Fit it on the d.c. side of a PV installation, in the array junction box or at the inverter d.c. input, on commercial rooftop systems, ground-mounted arrays, agricultural and industrial roof installations, and PV on buildings with a lightning protection system. Arrays present a large collecting area on an exposed roof, so d.c. surge protection is normally the first thing specified alongside the inverter.

Compliance

Tested as a Type 2 photovoltaic SPD to EN 50539-11, with UL and CSA approvals, a UL 94 V-0 enclosure and IP20 protection for mounting inside an enclosure. BS 7671 requires the risk from transient overvoltages to be assessed, and the d.c. side of a PV system is normally protected as well as the a.c. side.

Order today for fast UK dispatch on genuine DEHN PV surge protection at trade-direct prices.